| ◆ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
A1 | Commercial Private OfficeVacancy Sensor · Manual-On · Auto-Off 15 min · C405.2.1.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | VACANCY SENSOR REQUIRED per C405.2.1 (item 8: enclosed offices) + C405.2.1.1: manual-on, auto-off within 15 min. DIMMING REQUIRED per C405.2.3 item 10 (offices). AUTO RECEPTACLE per C405.13 item 1.1 — ≥50% of 125V outlets. DEMAND RESPONSIVE per C405.2.8 if bldg Group B ≥10,000 SF. C408.3: commissioning required. | 30–50 fc avg ANSI/IES RP-1-24 §4.1 |
A2 | Commercial Private OfficeVacancy Sensor · Manual-On · Auto-Off 15 min | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | VACANCY SENSOR per C405.2.1.1: manual-on, auto-off ≤15 min, manual off switch required. DIMMING per C405.2.3 item 10: 100%→10% continuous. PLUG LOAD per C405.13 item 1.1. C408.3: all controls commissioned. | 30–50 fc avg ANSI/IES RP-1-24 §4.1 |
A3 | Commercial Private OfficeAuto-On ≤50% · Occ Sensor | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | AUTO-ON ≤50% per C405.2.1.1 Exception 1 — full auto-on ≤50% power permitted in lieu of manual-on. Auto-off ≤15 min. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 item 1.1. C405.2.8: demand-responsive where bldg Group B ≥10,000 SF. | 30–50 fc avg ANSI/IES RP-1-24 §4.1 |
A4 | Private Office · Daylight + VacancyPerimeter Office · C405.2.3 Daylight | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | ▧ | — | — | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | VACANCY + DAYLIGHT per C405.2.1.1 + C405.2.4: daylight responsive REQUIRED if >75W in primary sidelit zone. DIMMING per C405.2.3 item 10. Automated shades integrate with daylight sensor. PLUG LOAD per C405.13 item 1.1. C408.3. | 30–50 fc avg Perim: 50 fc ANSI/IES RP-1-24 §4.1 |
A5 | Open Office ≤300 SFVacancy Sensor · C405.2.1.3 Not Required | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.56C405.3 T.C405.3.2(2) | Open office ≤300 SF: VACANCY SENSOR per C405.2.1 item 17 (enclosed ≤300 SF) + C405.2.1.1: manual-on, auto-off. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 items 1.6–1.7. C405.2.8 demand-responsive. | 30–50 fc avg ANSI/IES RP-1-24 §4.2 |
A6 | Open Office ≥300 SFZone Controls REQUIRED — C405.2.1.3 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | ⊞§2.1.3 | — | 🔌§405.13 | 0.56C405.3 T.C405.3.2(2) | Open plan ≥300 SF: C405.2.1.3 REQUIRED — zone controls ≤600 SF each; unoccupied zones auto-on ≤20%; auto-off all zones ≤15 min. PARTITION SENSORS per zone. AUTO-ON ≤50% within zone. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 items 1.6–1.7. C405.2.8. | 25–40 fc avg ANSI/IES RP-1-24 §4.2 |
A7 | Conference / Meeting RoomVacancy Sensor REQUIRED · AV Integration | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.88C405.3 T.C405.3.2(2) | Conference/meeting room: C405.2.1 item 3 requires occ sensor. C405.2.1.1 Exception 2: VACANCY (manual-on) SPECIFICALLY REQUIRED — full auto-on NOT permitted for conference rooms. DIMMING per C405.2.3 item 2. PLUG LOAD per C405.13 item 1.2. | 30–50 fc avg ANSI/IES RP-1-24 §5 |
A8 | Open Office · Full IntegrationDaylight + AV + Tunable White · C405.2.1.3 | — | 50§2.1 | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | ⊞§2.1.3 | ≋ | 🔌§405.13 | 0.56C405.3 T.C405.3.2(2) | Open office full integration: C405.2.1.3 zone controls + auto-on ≤20%. DAYLIGHT per C405.2.4 (>75W sidelit). DIMMING per C405.2.3. Tunable white (circadian/wellness, not code-mandated). PARTITION sensors. PLUG LOAD per C405.13. C405.2.8. | 25–40 fc avg ANSI/IES RP-1-24 §4.2 |
A9 | Conference · Full IntegrationDaylight + AV + Shades + Tunable White | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | ▧ | — | ≋ | 🔌§405.13 | 0.88C405.3 T.C405.3.2(2) | Conference full integration: C405.2.1.1 Exc 2: VACANCY required. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 2. AV per C405.2.5 special application. Tunable white. PLUG LOAD per C405.13 item 1.2. C408.3. | 30–50 fc avg AV dim: 5–10 fc ANSI/IES RP-1-24 §5 |
A10 | Break Room / Pantry / LoungeVacancy Sensor REQUIRED · Manual-On Only | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.55C405.3 T.C405.3.2(2) | C405.2.1 item 5: BREAKROOMS require occ sensor. C405.2.1.1 Exc 2: manual-on/vacancy required. DIMMING per C405.2.3 item 9 (lounge/break rooms). PLUG LOAD per C405.13 item 1.4 (breakrooms). C405.2.8 demand-responsive. | 10–30 fc avg IES HB 10th Ed. |
A11 | Reception / Front of HousePrimary Entrance · Full Auto-On Permitted | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | Reception/lobby-type: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies). DIMMING per C405.2.3 item 8 (lobbies). DAYLIGHT per C405.2.4 if >75W sidelit. Tunable white (not code-mandated). C405.2.8 demand-responsive. C408.3. | 20–30 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
B1 | Residential Dwelling UnitLiving / Bedroom · Manual Only | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | — | — | 0.46C405.3 T.C405.3.2(2) | Dwelling unit: C405.2.10 Exception — dwelling units may use MANUAL controls (no occ sensor required). DIMMING per C405.2.3 still required. Wireless per tenant preference. C408.3: commissioning for any automated controls installed. | 5–20 fc avg IES HB 10th Ed. |
B2 | Residential Dwelling UnitTunable White · Circadian · Manual Only | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.46C405.3 T.C405.3.2(2) | Dwelling unit — tunable white: C405.2.10 Exception — manual controls. DIMMING per C405.2.3. Tunable white for circadian wellness (not code-mandated, voluntary). Wireless control. C408.3. | 5–20 fc avg IES HB 10th Ed. |
B3 | Residential Common Area / AmenityFull Auto-On · Safety Exception · C405.2.1.1 | ✓§2.1 | — | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | Residential common area: C405.2.1 occ sensor required (corridors/common). C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. DAYLIGHT per C405.2.4 if applicable. C408.3. | 10–20 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
C1 | Building Lobby · Primary EntranceFull Auto-On · C405.2.1.1 Exception | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | Building lobby: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies explicitly listed). DIMMING per C405.2.3 item 8 — REQUIRED for lobbies. DAYLIGHT per C405.2.4. C405.2.8 demand-responsive. Tunable white (not code-mandated). C408.3. | 20–30 fc avg ANSI/IES RP-1-24 §7 |
C2 | Amenity Space · Fitness / Club RoomOcc Sensor · AV · Tunable White | — | 50§2.1 | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | — | — | ≋ | — | 0.82C405.3 T.C405.3.2(2) | Amenity/fitness center: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 4 — REQUIRED for gymnasiums/fitness centers. DAYLIGHT per C405.2.4. AV for programming. Tunable white. C405.2.8. | 30–50 fc workout IES RP-6-15 §5 |
C3 | Multi-Use Amenity · Flex SpacePartition Sensor · AV · Daylight · Shades | — | 50§2.1 | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | ▧ | ⊞§2.1.3 | — | — | 0.88C405.3 T.C405.3.2(2) | Multi-use flex space: C405.2.1.3 zone controls per partition zone ≤600 SF. DIMMING per C405.2.3 item 2 (multipurpose). DAYLIGHT per C405.2.4. Automated shades + AV + partition sensors. C405.2.8. C408.3. | 20–50 fc avg ANSI/IES RP-1-24 §5 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
D1 | Corridor / Transition AreaOcc Sensor Dims to ≤50% — Full Shutoff NOT Permitted · C405.2.1.4 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | Corridor: C405.2.1.4 SPECIFIC RULE — occ sensor SHALL reduce to ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED. Exception: corridors <2 fc at darkest point exempt. DIMMING per C405.2.3 (space without C405.2.1.1 → item 11 applies). Wired zone control per segment. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 §4 |
D2 | Stairway / Interior Exit StairStairway · Full Auto-On Permitted · C405.2.1.1 Exception 1 | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.47C405.3 T.C405.3.2(2) | Interior stairway (non-exit): C405.2.1 item 15 — stairways require occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted (stairways). DIMMING per C405.2.3. NOTE: Interior EXIT stairways EXEMPT per C405.2 Exception 2. C408.3. | 5–10 fc avg NFPA 101 §7.9 |
D3 | Emergency Egress / Exit Path LightingEmergency Egress · EXEMPT from C405.2 Auto Controls · NEC 700 | — | — | — | — | ✋ | — | — | — | — | — | — | — | — | — | N/ANEC 700 Not in LPD | Emergency egress/exit path lighting. C405.2 Exception 2 — INTERIOR EXIT STAIRWAYS, RAMPS and PASSAGEWAYS are EXEMPT from C405.2.1 automatic controls. C405.2 Exception 3 — emergency lighting that is auto-off during normal operations is exempt. NEC Article 700 governs. Manual controls only. No dimming required. | 1 fc min path NFPA 101 §7.9 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
E1 | Exterior Entry / Walkway / PlazaAstronomical Timeclock REQUIRED · C405.2.6 | — | — | — | ⏱§2.2 | — | — | — | — | ☀§2.4 | — | — | — | — | — | N/AExterior C405.2.7 | Exterior entry/walkway: C405.2.7.1 — lights AUTO-OFF when daylight satisfies need. C405.2.7.3 — reduce ≥50% at midnight or 1hr after close or 15-min inactivity. Astronomical timeclock required. No occ sensor required for exterior. C408.3. | 2–5 fc avg ANSI/IES RP-8-25 §5 |
E2 | Exterior Parking Lot / Surface LotAstronomical Timeclock REQUIRED · ≥50% Setback | — | — | — | ⏱§2.2 | — | — | — | — | ☀§2.4 | — | — | — | — | — | N/AExterior C405.2.7 | Exterior parking lot: C405.2.7.1 daylight auto-off. C405.2.7.3: luminaires >40W at ≤24 ft mounting — reduce ≥50% when no activity for 15 min. Astronomical timeclock for dusk-to-dawn. C408.3. | 2–5 fc avg ANSI/IES RP-8-25 §6 |
E3 | Exterior Facade / ArchitecturalAstronomical Timeclock · Curfew Shutoff Required | — | — | — | ⏱§2.2 | — | — | — | — | — | — | — | — | — | — | N/AExterior C405.2.7 | Exterior facade/architectural: C405.2.7.2 SPECIFIC — facade lighting SHALL auto-off when daylight adequate OR not later than 1hr after building close. For 24-hr buildings: off at midnight. NYC Zone 3/4 exception for special events at commissioner discretion. Timeclock required. | 0.5–3 fc avg IES G-1 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
F1 | Retail Sales FloorVacancy Sensor · Dimming · Daylight | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.85C405.3 T.C405.3.2(2) | Retail sales floor: C405.2.1 item 17 — spaces ≤300 SF enclosed require occ sensor. Larger retail: C405.2.2 time-switch required if no occ sensor. VACANCY sensor shown. DIMMING per C405.2.3 item 11 (spaces without C405.2.1.1). C405.2.8 demand-responsive if Group M ≥10,000 SF. | 30–50 fc avg IES RP-2-20 §4 |
F2 | Retail Sales Floor · DaylitVacancy Sensor + Continuous Daylight Dim | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | — | — | 0.85C405.3 T.C405.3.2(2) | Retail — daylit: VACANCY sensor. DAYLIGHT per C405.2.4 REQUIRED where >75W in sidelit/toplit zone. C402.5.2.2: skylight haze factor >90% for retail. DIMMING per C405.2.3. C405.2.8 demand-responsive. C408.3. | 30–50 fc avg IES RP-2-20 §4 |
F3 | Retail Fitting RoomVacancy Sensor REQUIRED · Tunable White | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | — | — | — | — | — | — | 0.45C405.3 T.C405.3.2(2) | Retail fitting room: C405.2.1 item 17 — enclosed ≤300 SF requires occ sensor. C405.2.1.1 Exc 2: manual-on/vacancy required (enclosed ≤300 SF). DIMMING per C405.2.3. C408.3. | 30–50 fc avg IES RP-2-20 §5 |
F4 | Retail — Hair / Nail SalonVacancy Sensor · High-Task Illumination · Retail LPD | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 0.75C405.3 T.C405.3.2(2) | C405.2.1 item 17 (≤300 SF) or sales-floor occ sensor. Vacancy sensor. C405.2.3 — dimming required. Tunable white highly recommended for color accuracy (CRI ≥90, 3500–4000K). Table C405.3.2(2): hair salon 0.65 W/SF, nail salon 0.75 W/SF — use higher. C405.2.8 demand-responsive. C408.3. | 50–75 fc avg Station: 75 fc IES RP-2-20 §5 |
F5 | Retail — Mall ConcourseTime-Switch REQUIRED · Dimming · C405.2.2 | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.57C405.3 T.C405.3.2(2) | Mall concourse — common circulation. Not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required (spaces without C405.2.1.1). C405.2.8 demand-responsive (Group M ≥10,000 SF). Table C405.3.2(2): mall concourse 0.57 W/SF. C408.3. | 20–30 fc avg IES RP-2-20 §4 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
G1 | Restaurant / Dining RoomManual Scene Control · Timeclock Required | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.76C405.3 T.C405.3.2(2) | Restaurant — leisure dining: C405.2.1 does NOT list leisure dining → C405.2.2 TIME-SWITCH REQUIRED (7-day clock, holiday shutoff, 2-hr override max). DIMMING per C405.2.3 item 3 — REQUIRED for dining areas (bar/lounge, leisure, family). C405.2.8 demand-responsive. C408.3. | 15–30 fc avg IES HB 10th Ed. |
G2 | Commercial Kitchen / Prep AreaOcc Sensor · Auto-On ≤50% · High CRI | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 1.19C405.3 T.C405.3.2(2) | Commercial kitchen: C405.2.1 occ sensor (food prep/enclosed workspace). Auto-on ≤50%. DIMMING per C405.2.3. C405.2.5 Exception: permanently installed task lighting over equipment exempt from specific app controls. C405.2.8. | 50 fc avg IES HB 10th Ed. |
G3 | Bar / Counter Service AreaVacancy Sensor · Manual Dim · Timeclock | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.76C405.3 T.C405.3.2(2) | Bar/counter service: C405.2.3 item 3 — DIMMING REQUIRED for bar/lounge dining areas. C405.2.1 occ sensor (lounge). Vacancy sensor. C405.2.8 demand-responsive. Wired + wireless for scene management. C408.3. | 15–30 fc avg IES HB 10th Ed. |
G4 | Family Dining RoomTime-Switch REQUIRED · Dimming REQUIRED · C405.2.3 Item 3 | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.52C405.3 T.C405.3.2(2) | Family dining room. C405.2.1 does NOT list family dining → C405.2.2 TIME-SWITCH REQUIRED. C405.2.3 item 3 — DIMMING REQUIRED for dining areas (family dining listed). Scene control via time-switch + dimming presets. Table C405.3.2(2): dining area — family 0.52 W/SF. C408.3. | 15–30 fc avg IES HB 10th Ed. |
G5 | Cafeteria / Fast Food DiningOcc Sensor REQUIRED · Zone Controls ≥300 SF · C405.2.1.3 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 0.36C405.3 T.C405.3.2(2) | C405.2.1 item 6 — cafeteria and fast-food dining REQUIRE occ sensor. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF; auto-on ≤20% unoccupied zones. C405.2.3 item 3 — dimming required (cafeteria). AV for programming. C405.2.8 demand-responsive. Table C405.3.2(2): dining — cafeteria/fast food 0.36 W/SF. C408.3. | 20–30 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
H1 | Patient Room · General / Med-SurgManual Only · Patient Safety Exception | — | — | — | — | ✋ | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 0.78C405.3 T.C405.3.2(2) | Patient room: C405.2 Exception 1 — auto-shutoff could endanger patient safety → MANUAL controls acceptable. C405.2.2 Exception 2 — patient care spaces exempt from time-switch. DIMMING per C405.2.3 item 5 — REQUIRED (healthcare patient rooms). Tunable white for circadian. C408.3. | 5 fc rest / 30 fc exam ANSI/IES RP-29-25 §5 |
H2 | Patient Room · Perimeter DaylightManual + Daylight + Shades + Tunable White | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | ☀§2.4 | — | ▧ | — | ≋ | — | 0.78C405.3 T.C405.3.2(2) | Patient room — daylit: C405.2 Exception 1 — manual controls. DIMMING per C405.2.3 item 5. DAYLIGHT per C405.2.4 — REQUIRED (>75W sidelit). Note: C405.2.4 Exception 1 exempts patient CARE areas — lobbies/daylit rooms w/o care not exempt. Automated shades. Tunable white. | 5 fc rest / 30 fc exam ANSI/IES RP-29-25 §5 |
H3 | ICU / Critical Care RoomPatient Safety Exception · Multi-Scene · Tunable White | — | — | — | — | ✋ | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 0.78C405.3 T.C405.3.2(2) | ICU/critical care: C405.2 Exception 1 — MANUAL CONTROLS REQUIRED (auto-shutoff endangers critical patient safety). C405.2.2 Exception 2: exempt from time-switch. DIMMING per C405.2.3 item 5. Tunable white for circadian/staff workflow. C408.3. | 5 fc rest / 50 fc exam ANSI/IES RP-29-25 §7 |
H4 | Exam Room / Consultation RoomVacancy Sensor · Patient Privacy · High CRI | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 1.33C405.3 T.C405.3.2(2) | Exam/consultation room: C405.2.1 item 17 (≤300 SF enclosed) — occ sensor. C405.2.1.1 Exc 2: VACANCY required. DIMMING per C405.2.3 item 5 — REQUIRED (exam rooms). C405.2.4 Exception 1: daylight controls EXEMPT for direct patient care. C408.3. | 50–75 fc avg ANSI/IES RP-29-25 §6 |
H5 | Telemedicine / Virtual Care RoomVacancy Sensor · Tunable White · High CRI | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | ≋ | — | 1.44C405.3 T.C405.3.2(2) | Telemedicine room: C405.2.1 item 13 — SPECIFICALLY LISTED: telemedicine rooms in healthcare REQUIRE occ sensor. C405.2.1.1 Exc 2: vacancy. DIMMING per C405.2.3 item 5. Tunable white for camera color accuracy. C408.3. | 50–75 fc avg ANSI/IES RP-29-25 §6 |
H6 | Nursing Station / Care Team HubOcc Sensor · Tunable White · Daylight | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 1.07C405.3 T.C405.3.2(2) | Nursing station: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 5 — REQUIRED (nurses' stations specifically listed). C405.2.4 Exception 1: daylight exempt for patient care. Tunable white for shift-work circadian. C408.3. | 30–50 fc avg ANSI/IES RP-29-25 §7 |
H7 | Pharmacy / Medication PreparationOcc Sensor · High CRI ≥90 Mandatory | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 1.59C405.3 T.C405.3.2(2) | Pharmacy: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 5 (healthcare). C405.2.4 Exception 1: daylight exempt for patient care. Wired control for precision task lighting. C408.3. | 50 fc avg ANSI/IES RP-29-25 §10 |
H8 | Healthcare CorridorFull Auto-On · Dim to ≤50% · C405.2.1.4 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.61C405.3 T.C405.3.2(2) | Healthcare corridor: C405.2.1.4 — REDUCE TO ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED (patient safety). DIMMING per C405.2.3 item 11. Wired zone control per corridor segment. C405.2.8. C408.3. | 5–10 fc avg ANSI/IES RP-29-25 §4 |
H9 | Healthcare Lobby / WaitingFull Auto-On · Tunable White · Daylight | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | Healthcare lobby: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies). DIMMING per C405.2.3 item 8 — REQUIRED. C405.2.4: daylight responsive — lobby is NOT direct patient care so Exception 1 does NOT apply here. Tunable white for wellness. C408.3. | 15–30 fc avg ANSI/IES RP-29-25 §4 |
H10 | Medical Supply / Storage RoomVacancy Sensor REQUIRED · High CRI | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.54C405.3 T.C405.3.2(2) | C405.2.1 item 7 — SPECIFICALLY LISTED: medical supply rooms in healthcare REQUIRE occ sensor. C405.2.1.1: vacancy sensor (manual-on, auto-off ≤15 min). DIMMING per C405.2.3. C408.3. | 30 fc avg ANSI/IES RP-29-25 §8 |
H11 | Nursing Home / LTC Resident RoomPatient Safety Exception · Tunable White | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.78C405.3 T.C405.3.2(2) | LTC/nursing home resident room: C405.2 Exception 1 — resident safety, manual controls. C405.2.3 dimming required. C405.2.10 residential exception may also apply. Tunable white for circadian/dementia care (not code-mandated). C408.3. | 5 fc rest / 20 fc task ANSI/IES RP-29-25 §5 |
H12 | Senior / Assisted Living UnitResidential Exception · Tunable White | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.78C405.3 T.C405.3.2(2) | Senior/assisted living: C405.2 Exception 1 + C405.2.10 residential exception — manual controls. DIMMING per C405.2.3. Tunable white for circadian health (not code-mandated). C408.3. | 5 fc rest / 20 fc task ANSI/IES RP-29-25 §5 |
H13 | Rehabilitation / Therapy AreaVacancy Sensor · Patient Privacy · Daylight | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | Rehab/physical therapy: C405.2.1 occ sensor. Vacancy sensor. DIMMING per C405.2.3 item 5 — REQUIRED (physical therapy rooms listed). C405.2.4 Exception 1: daylight exempt for direct patient care. C408.3. | 30–50 fc avg ANSI/IES RP-29-25 §9 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
I1 | Operating Room / Procedure RoomPatient Safety Exception · Manual Scene Control | — | — | — | — | ✋ | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 2.26C405.3 T.C405.3.2(2) | Operating room: C405.2 Exception 1 — MANUAL CONTROLS REQUIRED (auto-shutoff endangers patient life safety). C405.2.2 Exception 2: exempt from time-switch (direct patient care). DIMMING per C405.2.3 item 5 (imaging/procedure). No occ sensor. C408.3. | 100–200 fc field / 5 fc rest ANSI/IES RP-29-25 §12 |
I2 | Endoscopy / Interventional SuitePatient Safety Exception · Manual Scene Control | — | — | — | — | ✋ | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 2.26C405.3 T.C405.3.2(2) | Endoscopy/interventional suite: C405.2 Exception 1 — manual controls only. C405.2.2 Exception 2. DIMMING per C405.2.3 item 5. Wired precision dimming for procedure visualization. C408.3. | 75–150 fc avg ANSI/IES RP-29-25 §12 |
I3 | Sterile Processing / CSPDOcc Sensor · Auto-On ≤50% · High CRI ≥90 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 1.19C405.3 T.C405.3.2(2) | Sterile processing/CSPD: not direct patient care — occ sensor required. C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3. Wired control for task zone management. C408.3. | 50 fc avg ANSI/IES RP-29-25 §11 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
J1 | Classroom — Standard K-12Vacancy Sensor REQUIRED — C405.2.1 Mandatory List | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 0.72C405.3 T.C405.3.2(2) | C405.2.1 item 1 — classrooms REQUIRE occ sensor. C405.2.1.1 Exception 2 — VACANCY (manual-on) SPECIFICALLY REQUIRED for classrooms (full auto-on not permitted). DIMMING per C405.2.3 item 1 — REQUIRED. C405.13 item 1.5 — auto receptacle required. C405.2.8 demand-responsive. | 30–50 fc avg ANSI/IES RP-3-20 §4 |
J2 | Classroom · Daylit — K-12Vacancy Sensor + Continuous Daylight Dim · C405.2.3 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | — | 🔌§405.13 | 0.72C405.3 T.C405.3.2(2) | Classroom — daylit: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4 — REQUIRED where >75W in daylight zone. DIMMING per C405.2.3 item 1. C405.13 auto receptacle. Daylight + vacancy sensors for maximum savings. | 30–50 fc avg Perim: 50 fc ANSI/IES RP-3-20 §4 |
J3 | Shop / Lab Classroom — K-12Vacancy Sensor Req'd · Timeclock Exempt | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 1.04C405.3 T.C405.3.2(2) | Shop/lab classroom: C405.2.1 item 1. C405.2.1.1 Exception 2 — shop classrooms and laboratory classrooms EXEMPT from manual-on requirement → auto-on ≤50% permitted. DIMMING per C405.2.3 item 1. C405.13 auto receptacle. C408.3. | 30–50 fc avg ANSI/IES RP-3-20 §4 |
J4 | Classroom · Full Integration — K-12Daylight + AV + Tunable White · C405.2.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | — | — | ≋ | 🔌§405.13 | 0.72C405.3 T.C405.3.2(2) | Classroom — full integration: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4. DIMMING per C405.2.3 item 1. AV per C405.2.5 special application. Tunable white for learning. C405.13 auto receptacle. Full BMS. C408.3. | 30–50 fc avg ANSI/IES RP-3-20 §4 |
J5 | Natatorium / Indoor Pool — K-12Safety Exception · Full Auto-On | ✓§2.1 | — | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | — | — | 0.99C405.3 T.C405.3.2(2) | Natatorium K-12: C405.2.1 occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted (safety environment). DIMMING per C405.2.3. DAYLIGHT per C405.2.4 (skylights). Wireless for wet environment. C408.3. | 50 fc avg surface IES RP-6-15 §6 |
J6 | Gymnasium — K-12Occ Sensor · AV · Daylight | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | Gymnasium K-12: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 4 — REQUIRED for gymnasiums. DAYLIGHT per C405.2.4 (skylights). AV for events/scoring. C405.2.8 demand-responsive. C408.3. | 30–50 fc practice IES RP-6-15 §4 |
J7 | Cafeteria / Dining Hall — K-12Occ Sensor REQUIRED — C405.2.1 Mandatory List | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 0.36C405.3 T.C405.3.2(2) | Cafeteria K-12: C405.2.1 item 6 — cafeteria requires occ sensor. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF. DIMMING per C405.2.3 item 3 (cafeteria dining). AV for events. C405.2.8 demand-responsive. C408.3. | 20–30 fc avg IES HB 10th Ed. |
J8 | Cafetorium — K-12Cafetorium (Cafeteria + Auditorium) · Zone Controls · Dimming Required | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | Cafetorium (combined cafeteria/auditorium hybrid space). Compliance path: use higher LPD (gym playing area 0.82 W/SF (2025 NYCECC)) to cover all modes. C405.2.1 item 6 (cafeteria) — occ sensor required. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF. C405.2.3 item 3 — dimming required (dining) and item 2 (auditorium use). AV integration for assembly use. C405.2.8 demand-responsive. C408.3. | 20–50 fc avg ANSI/IES RP-3-20 + HB |
J9 | Gymnastorium — K-12Gymnastorium (Gymnasium + Auditorium) · Dimming Required · AV Integrated | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | Gymnastorium (combined gymnasium/auditorium). Use gymnasium playing area LPD 0.75 W/SF. C405.2.1 occ sensor. Auto-on ≤50%. C405.2.3 item 4 — dimming REQUIRED (gymnasium). C405.2.4 daylight responsive if skylights present. AV integration for assembly/event use. Scene control for gym vs. assembly modes. C405.2.8. C408.3. | 30–75 fc avg Sport: 50–75 fc IES RP-6-15 + HB |
J10 | Laboratory Classroom — K-12Vacancy Sensor REQUIRED · High-Task Illumination · C405.2.1 Item 1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | 🔌§405.13 | 1.04C405.3 T.C405.3.2(2) | C405.2.1 item 1 — classrooms/training rooms require occ sensor. C405.2.1.1 Exception 2 — NOTE: laboratory classrooms are EXEMPT from the manual-on requirement; auto-on ≤50% permitted. C405.2.3 item 1 — dimming required. C405.13 item 1.5 — auto receptacle. Per Table C405.3.2(2): "Laboratory — in or as a classroom" = 1.04 W/SF. C408.3. | 50–75 fc avg Bench: 75 fc ANSI/IES RP-3-20 §4 |
J11 | Art / Maker Space — K-12Vacancy Sensor REQUIRED · High CRI · Task + Ambient · C405.2.1 Item 1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 1.04C405.3 T.C405.3.2(2) | C405.2.1 item 1 — classroom/training rooms. C405.2.1.1 Exception 2 — art rooms (non-shop/lab) require manual-on (vacancy). C405.2.3 item 1 — dimming required. Tunable white for color accuracy (CRI ≥90, 3500–5000K range). Use laboratory classroom LPD 1.04 W/SF as closest space type. C408.3. | 50 fc avg Task: 75 fc ANSI/IES RP-3-20 §4 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
K1 | Lecture Hall / AuditoriumVacancy Sensor · AV Integrated · Daylight | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | — | — | — | 0.72C405.3 T.C405.3.2(2) | Lecture hall: C405.2.1 item 1 — classrooms/lecture. C405.2.1.1 Exc 2: VACANCY required. DIMMING per C405.2.3 item 1 — REQUIRED. DAYLIGHT per C405.2.4. AV integration for presentations. C405.2.8. C408.3. | 30–50 fc avg ANSI/IES RP-3-20 §5 |
K2 | Library / Study CommonsOcc Sensor · Tunable White · Daylight | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.86C405.3 T.C405.3.2(2) | Library/study commons: C405.2.1 occ sensor. DIMMING per C405.2.3 item 7 — REQUIRED for library reading rooms. DAYLIGHT per C405.2.4. Tunable white for reading. C405.2.8 demand-responsive. C408.3. | 30–50 fc avg ANSI/IES RP-30-25 §5 |
K3 | University Athletics / Gym / Rec CenterOcc Sensor · AV · Daylight | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | University gym/rec: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 — REQUIRED (gyms/fitness centers). DAYLIGHT per C405.2.4. AV for events. C405.2.8 demand-responsive. C408.3. | 30–50 fc avg IES RP-6-15 §4 |
K4 | Natatorium / Indoor Pool — UniversitySafety Exception · Full Auto-On | ✓§2.1 | — | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | — | — | 0.99C405.3 T.C405.3.2(2) | University natatorium: C405.2.1 occ sensor. C405.2.1.1 Exc 1 — full auto-on (safety). DIMMING per C405.2.3. DAYLIGHT per C405.2.4 (skylights). Wireless for wet environment. C408.3. | 50 fc avg surface IES RP-6-15 §6 |
K5 | Field House / ArenaOcc Sensor · AV · Daylight | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | Field house/arena: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 (large gym). DAYLIGHT per C405.2.4. AV for events. C405.2.8 demand-responsive. Zone control per luminaire group. C408.3. | 75–100 fc playing IES RP-6-15 §3 |
K6 | Cafeteria / Dining Hall — UniversityOcc Sensor REQUIRED · AV Integration | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 0.36C405.3 T.C405.3.2(2) | University cafeteria: C405.2.1 item 6. C405.2.1.3 zone controls ≥300 SF. DIMMING per C405.2.3 item 3 (cafeteria dining). AV. C405.2.8 demand-responsive. C408.3. | 20–30 fc avg IES HB 10th Ed. |
K7 | University / Research LaboratoryVacancy Sensor · High Task Illumination · Lab LPD 1.21 W/SF | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | — | 🔌§405.13 | 1.21C405.3 T.C405.3.2(2) | C405.2.1 item 17 (≤300 SF) or item 1 (classroom/lab). C405.2.1.1 — vacancy sensor (manual-on). C405.2.3 — dimming required. C405.2.4 — daylight responsive where >75W sidelit. C405.13 auto receptacle (lab workstations = individual workstations per 1.7). Table C405.3.2(2): "Laboratory — otherwise" = 1.21 W/SF. C408.3. | 50–100 fc avg Bench: 75–100 fc ANSI/IES RP-3-20 §6 |
K8 | Cafetorium — UniversityCafetorium · Zone Controls REQUIRED ≥300 SF · C405.2.1.3 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 0.82C405.3 T.C405.3.2(2) | University cafetorium (cafeteria + auditorium). C405.2.1 item 6 — occ sensor required. C405.2.1.3 ≥300 SF zone controls. C405.2.3 items 2 + 3 — dimming required. AV for assembly. Use gymnasium playing area LPD 0.75 W/SF. C405.2.8 demand-responsive (Group E ≥10,000 SF). C408.3. | 20–50 fc avg ANSI/IES RP-3-20 + HB |
K9 | Dormitory Living QuartersC405.2.10 Exception — Manual Controls Permissible · Dimming Required | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.46C405.3 T.C405.3.2(2) | Dormitory living quarters. C405.2.10 Exception — dwelling/sleeping units may use manual controls. C405.2.3 — dimming still required. Tunable white for circadian wellness (not code-mandated). C405.3.3: lamp efficacy requirements apply. Table C405.3.2(2): "Dormitory — living quarters" = 0.46 W/SF. C408.3. | 5–30 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
L1 | Museum / GalleryManual Scene · Timeclock · Tunable White | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 0.31C405.3 T.C405.3.2(2) | Museum/gallery: NOT in C405.2.1 mandatory list → C405.2.2 TIME-SWITCH REQUIRED. DIMMING per C405.2.3 item 11 (spaces without C405.2.1.1). C405.2.5 Exception: display/accent/track lighting EXEMPT (special application). Tunable white for conservation. C408.3. | 5–30 fc exhibit IES HB 10th Ed. |
L2 | Transit Hub / Transportation CenterFull Auto-On · Safety · Daylight | ✓§2.1 | — | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | Transit hub: C405.2.1 occ sensor (public space). C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. 24-hr operation consideration. C405.2.8 demand-responsive. C408.3. | 10–20 fc avg ANSI/IES RP-10-20 §4 |
L3 | Performance Venue / AuditoriumManual Scene · Timeclock · AV · TW | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | ≋ | — | 1.09C405.3 T.C405.3.2(2) | Performance venue: C405.2.2 TIME-SWITCH required (not in C405.2.1 list). DIMMING per C405.2.3 item 11. C405.2.5 Exception: theatrical/performance lighting with automated scene control EXEMPT from C405.2.3. AV integration. Tunable white. C408.3. | 10–20 fc seating IES HB 10th Ed. |
L4 | Courthouse / Government OfficeOcc Sensor · Daylight · Security Exception | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | — | — | 1.06C405.3 T.C405.3.2(2) | Courthouse/gov office: C405.2.1 item 8 (offices). Auto-on ≤50%. DIMMING per C405.2.3 item 10 (offices). DAYLIGHT per C405.2.4. C405.2.8 demand-responsive (Group B). C408.3. | 50–75 fc avg IES HB 10th Ed. |
L5 | CourtroomOcc Sensor · High-Task Illumination · Courtroom LPD 1.08 W/SF | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | — | — | 1.08C405.3 T.C405.3.2(2) | C405.2.1 occ sensor (enclosed space). Auto-on ≤50%. C405.2.3 — dimming required. AV integration for video proceedings. C405.2.8 demand-responsive (Group B courthouse). Table C405.3.2(2): "Courtroom" = 1.08 W/SF (2025 NYCECC). C408.3. | 50–75 fc avg Bench: 75 fc IES HB 10th Ed. |
L6 | Religious Building — Worship / Choir / PulpitTime-Switch REQUIRED · Scene Control · Special Application Exception | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | ≋ | — | 0.75C405.3 T.C405.3.2(2) | Religious worship space — not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required. C405.2.5 — theatrical/performance lighting for worship is special application (scene control exempt). AV. Tunable white for atmosphere. Table C405.3.2(2): religious — worship/pulpit/choir 0.75 W/SF. C408.3. | 30–50 fc avg Choir: 50 fc IES HB 10th Ed. |
L7 | Religious Building — Fellowship HallTime-Switch REQUIRED · Dimming Required · Multi-Purpose Use | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.50C405.3 T.C405.3.2(2) | Fellowship hall / multipurpose religious space. C405.2.2 time-switch required. C405.2.3 item 11 — dimming required. Table C405.3.2(2): religious buildings — fellowship hall 0.50 W/SF. C408.3. | 20–30 fc avg IES HB 10th Ed. |
L8 | Convention Center — Exhibit SpaceTime-Switch REQUIRED · Dimming · C405.2.8 Demand-Responsive | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.50C405.3 T.C405.3.2(2) | Convention center exhibit hall. Not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required. C405.2.8 demand-responsive (Group B/M ≥10,000 SF). C405.2.5 display/accent lighting exempt. Table C405.3.2(2): convention center exhibit space 0.50 W/SF. C408.3. | 30–50 fc avg Exhibit: 50 fc IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
M1 | Interior Parking Garage — StandardC405.2.4 Garage Controls · Safety · Full Auto-On | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 0.11C405.3 T.C405.3.2(2) | C405.2.9 — SPECIFIC PARKING CONTROLS: occ sensor + auto-reduce ≥30% in each zone (≤3,600 SF) within 15 min. C405.2.9 item 3: within 20 ft of wall openings — auto-reduce ≥50% in response to daylight. C405.2.9 item 2: eye adaptation at entries — reduce ≥50% sunset to sunrise. DIMMING per C405.2.3. | 5–10 fc avg ANSI/IES RP-10-20 §4 |
M2 | Interior Parking Garage — Vacancy PathManual-On · Safety Dim · C405.2.4 | — | — | ◉§2.1 | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 0.11C405.3 T.C405.3.2(2) | C405.2.9 parking controls. Vacancy sensor option per C405.2.1.1. Auto-reduce ≥30% per zone. DAYLIGHT per C405.2.4 at openings. DIMMING per C405.2.3. C408.3. | 5–10 fc avg ANSI/IES RP-10-20 §4 |
M3 | Parking Garage · Daylit Entry RampsDaylight at Ramps · C405.2.3 + C405.2.4 | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 1.06C405.3 T.C405.3.2(2) | C405.2.9 item 2: entry ramp eye-adaptation lighting — SEPARATELY CONTROLLED, reduce ≥50% from sunset to sunrise. C405.2.9 item 3: within 20 ft of perimeter openings — daylight-responsive ≥50% reduction. C405.2.3 dimming. C408.3. | 10–20 fc transition ANSI/IES RP-10-20 §4 |
M4 | Parking Garage · Ingress/Egress ZoneDark Adaptation Zone · Safety · C405.2.4 | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 1.06C405.3 T.C405.3.2(2) | Dark adaptation zone: C405.2.9 item 2 — REQUIRED separate control at vehicle entrances; reduce ≥50% from sunset to sunrise. C405.2.9 item 3 daylight at openings. DIMMING per C405.2.3. C408.3. | 10–20 fc transition ANSI/IES RP-10-20 §4 |
M5 | Open-Air / Surface Parking LotAstronomical Timeclock REQUIRED · C405.2.6 | — | — | — | ⏱§2.2 | — | — | — | — | ☀§2.4 | — | — | — | — | — | N/AExterior C405.2.7 | Surface parking lot — exterior: C405.2.7.1 auto-off when daylight adequate. C405.2.7.3: luminaires >40W at ≤24 ft — reduce ≥50% when no activity for 15 min. Astronomical timeclock. Daylight sensor. C408.3. | 2–5 fc avg ANSI/IES RP-8-25 §6 |
M6 | Parking Garage · Stair / Elevator CoreFull Auto-On · Life Safety · C405.2.1.4 | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | — | — | — | — | — | — | 0.47C405.3 T.C405.3.2(2) | Garage stair/elevator core: C405.2.1 item 15 — stairways require occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. C405.2 Exception 2: life safety paths within exit stairways exempt from auto-off. C408.3. | 5–10 fc avg NFPA 101 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
N1 | Warehouse — General Storage (High-Bay)C405.2.1.2 Warehouse Rule · ≥50% Reduction | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | ☀§2.4 | — | — | — | — | — | 1.24C405.3 T.C405.3.2(2) | C405.2.1 item 16: warehouse storage REQUIRES occ sensor. C405.2.1.2 SPECIFIC: each AISLEWAY controlled independently; auto-reduce to ≤30% (not full-off) within 15 min; backup time-switch for non-sensored areas; manual off provided. DAYLIGHT at skylights per C405.2.4. C405.2.8. | 20–30 fc avg IES RP-7-22 §5 |
N2 | Warehouse — Daylit High-BaySkylights · C405.2.1.2 + C405.2.3 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | ☀§2.4 | — | — | — | — | — | 1.24C405.3 T.C405.3.2(2) | C405.2.1.2 aisle-by-aisle controls. DAYLIGHT per C405.2.4 — REQUIRED at skylights. C402.5.2.2: skylight haze factor >90% for warehouse. Combined daylight + occ sensor. DIMMING per C405.2.3. C405.2.8. C408.3. | 20–30 fc avg IES RP-7-22 §5 |
N3 | Loading Dock / Receiving AreaC405.2.1.2 · Daylight at Dock Doors | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | ☀§2.4 | — | — | — | — | — | 0.51C405.3 T.C405.3.2(2) | Loading dock: C405.2.1.2 warehouse controls apply. DAYLIGHT per C405.2.4 at dock doors. DIMMING per C405.2.3. Zone control per dock bay. C405.2.8 demand-responsive. C408.3. | 20–30 fc avg IES RP-7-22 §7 |
N4 | Warehouse Mezzanine Office / Break RoomVacancy Sensor · Commercial Office Rules Apply | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | Mezzanine office/break room: C405.2.1 items 5 and 8 (breakroom + office). C405.2.1.1 Exc 2: vacancy. DIMMING per C405.2.3. C405.13 auto receptacle (office/break). C405.2.8. C408.3. | 30–50 fc avg ANSI/IES RP-1-24 §4 |
N5 | Cold Storage / Freezer WarehouseManual-On · Low-Temp Fixtures | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.35C405.3 T.C405.3.2(2) | Cold storage/freezer: C405.2.1 item 12 — storage rooms require occ sensor. Vacancy sensor (manual-on for cold entry). DIMMING per C405.2.3. Wired for cold-rated fixtures. Manual-on accommodates glove use in cold environment. C408.3. | 10–20 fc avg IES RP-7-22 §5 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
O1 | Data Center — Server / Computer RoomSafety + Continuous Operation Exception · C405.2.2 | — | — | — | — | ✋ | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.75C405.3 T.C405.3.2(2) | C405.2.1 item 2 — data centers require occ sensor. C405.2 Exception 1: 24/7 continuous operations — auto-shutoff would endanger systems → MANUAL controls permissible. DIMMING per C405.2.3. Wired control for precision lighting management. C408.3. | 20–30 fc avg IES HB 10th Ed. |
O2 | Data Center — Network Operations CenterLow Auto-On · Occ Sensor · Screen Glare Control | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | — | — | 0.75C405.3 T.C405.3.2(2) | NOC/operations center: C405.2.1 item 2 — computer rooms require occ sensor. Auto-on ≤50%. DIMMING per C405.2.3. Wired + wireless. C405.2.8 demand-responsive. C408.3. | 30–50 fc avg IES HB 10th Ed. |
O3 | Data Center — Electrical / MechanicalVacancy Sensor · NEC 700 Emergency Required | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | C405.2.1 item 17: enclosed ≤300 SF. Vacancy sensor. DIMMING per C405.2.3. C405.2.5: task lighting for electrical work may qualify for special application. C408.3. | 20 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
P1 | Electrical Room / Switchgear / MCCVacancy Sensor · NEC 110.26(D) Override Required | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | C405.2.1 item 17: enclosed ≤300 SF — occ sensor. Vacancy (manual-on). DIMMING per C405.2.3. C405.2.5: task lighting exempt. NFPA 70E: manual control appropriate for arc flash safety. C408.3. | 20–30 fc avg IES HB 10th Ed. |
P2 | Main Mechanical Room / HVAC PlantVacancy Sensor · Override Required · NEC 110.26(D) | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | C405.2.1 occ sensor. Vacancy sensor. DIMMING per C405.2.3. C405.2.5 task lighting for mechanical work exempt. C408.3. | 20–30 fc avg IES HB 10th Ed. |
P3 | Generator Room / Emergency Power RoomEXEMPT — Manual Required · NFPA 37 · NFPA 110 | — | — | — | — | ✋ | — | — | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | Generator room: C405.2 Exception 1 — AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT SAFETY — EXEMPT from occ sensor requirements. Manual controls only. No dimming required (safety-critical/emergency space). C408.3. | 10–20 fc avg IES HB 10th Ed. |
P4 | Plumbing / Fire Sprinkler Valve RoomVacancy Sensor · NFPA 13 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | C405.2.1 item 17: enclosed ≤300 SF. Vacancy sensor. DIMMING per C405.2.3. NFPA 13 sprinkler access — manual-on appropriate. C408.3. | 20–30 fc avg IES HB 10th Ed. |
P5 | Utility Service Corridor / Basement HallFull Auto-On · C405.2.1.4 Dim to ≤50% | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | Utility corridor: C405.2.1 item 15 — corridors require occ sensor. C405.2.1.4: reduce to ≤50% within 15 min. DIMMING per C405.2.3 item 11. Wired zone control. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 §4 |
P6 | Basement / Below-Grade StorageVacancy Sensor REQUIRED · C405.2.1.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.35C405.3 T.C405.3.2(2) | C405.2.1 item 12 — storage rooms require occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3. | 10–20 fc avg IES HB 10th Ed. |
P7 | Janitor's Closet / Custodial RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.35C405.3 T.C405.3.2(2) | C405.2.1 item 18 — SPECIFICALLY LISTED: janitorial closets require occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3. | 10 fc avg IES HB 10th Ed. |
P8 | Telecom / IDF / MDF ClosetEXEMPT — Security + Continuous Operation · C405.2.2 | — | — | — | — | ✋ | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | Telecom/IDF/MDF: C405.2 Exception 1 — security systems require continuous lighting; auto-shutoff could endanger security operations — EXEMPT. Manual controls. DIMMING per C405.2.3. Wired for permanent installation. C408.3. | 10–20 fc avg IES HB 10th Ed. |
P9 | Restroom / Toilet Room / Locker RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1 | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.74C405.3 T.C405.3.2(2) | C405.2.1 item 11 — RESTROOMS specifically required. C405.2.1.1 Exception 1: full auto-on permitted for restrooms. DIMMING per C405.2.3. Wired multi-stall management. C408.3. | 20 fc avg IES HB 10th Ed. |
P10 | Copy / Print / Mail RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | 🔌§405.13 | 0.50C405.3 T.C405.3.2(2) | C405.2.1 item 4 — COPY/PRINT ROOMS specifically listed. C405.2.1.1 Exc 2: vacancy required. DIMMING per C405.2.3. C405.13 item 1.3 — AUTO RECEPTACLE REQUIRED for rooms used primarily for copy/print. C405.2.8. C408.3. | 30 fc avg IES HB 10th Ed. |
P11 | Laundry / Service RoomVacancy Sensor · Continuous Cycle Exception Possible | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.43C405.3 T.C405.3.2(2) | C405.2.1 item 9 — LAUNDRY/WASHING specifically listed. Vacancy sensor. DIMMING per C405.2.3. Wired for utility space. C408.3. | 20 fc avg IES HB 10th Ed. |
P12 | Workshop / Fabrication ShopVacancy Sensor · High-Task · Workshop LPD 1.09 W/SF | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 1.09C405.3 T.C405.3.2(2) | C405.2.1 item 17 (≤300 SF enclosed) or occ sensor for larger. Vacancy sensor. C405.2.3 — dimming required. C405.2.5 — task lighting over equipment may qualify as special application. Table C405.3.2(2): "Workshop" = 1.09 W/SF. C408.3. | 50–75 fc avg Bench: 75 fc IES HB 10th Ed. |
P13 | Locker Room / Changing RoomFull Auto-On Permitted · C405.2.1.1 Exception 1 · Dimming Required | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.43C405.3 T.C405.3.2(2) | C405.2.1 item 14 — locker rooms REQUIRE occ sensor. C405.2.1.1 Exception 1 — full auto-on permitted for locker rooms (explicitly listed). C405.2.3 — dimming required. Table C405.3.2(2): "Locker room" = 0.43 W/SF. C408.3. | 20–30 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
Q1 | Class A Open Office FloorZone Controls C405.2.1.3 · LL88 Submetering · LL97 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | 📽 | — | ⊞§2.1.3 | ≋ | 🔌§405.13 | 0.56C405.3 T.C405.3.2(2) | Class A open floor: C405.2.1.3 REQUIRED — zone controls ≤600 SF; auto-on ≤20% unoccupied zones; auto-off all zones ≤15 min. DAYLIGHT per C405.2.4. DIMMING per C405.2.3 item 10. AV. Partition sensors. Tunable white. C405.13 items 1.6–1.7. C405.2.8. | 25–40 fc avg ANSI/IES RP-1-24 §4.2 |
Q2 | Class A Private Office · PerimeterVacancy Sensor · Daylight · Shades · TW · LL97 | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | ▧ | — | ≋ | 🔌§405.13 | 0.73C405.3 T.C405.3.2(2) | Class A private office: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 10. Tunable white. C405.13 item 1.1 auto receptacle. C405.2.8. C408.3. | 30–50 fc avg ANSI/IES RP-1-24 §4.1 |
Q3 | Class A Conference RoomVacancy Sensor · AV · Daylight · Shades · LL88 | — | — | ◉§2.1 | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | ▧ | — | ≋ | 🔌§405.13 | 0.88C405.3 T.C405.3.2(2) | Class A conference: C405.2.1.1 Exc 2: vacancy required. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 2. AV. Tunable white. C405.13 item 1.2 auto receptacle. C405.2.8. C408.3. | 30–50 fc avg ANSI/IES RP-1-24 §5 |
Q4 | High-Rise Building LobbyFull Auto-On · Tunable White · LL88 Metered | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | High-rise lobby: C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3 item 8 — REQUIRED (lobbies). DAYLIGHT per C405.2.4. C405.2.8 demand-responsive. Tunable white for brand. C408.3. | 20–30 fc avg ANSI/IES RP-1-24 §7 |
Q5 | High-Rise Elevator Lobby / CoreFull Auto-On · Dim on Vacancy · C405.2.1.4 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.64C405.3 T.C405.3.2(2) | Elevator lobby/core: C405.2.1.4 — treated as corridor; reduce to ≤50% within 15 min; full shutoff NOT permitted. DIMMING per C405.2.3. Wired zone control per floor. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 |
Q6 | High-Rise Base Building CorridorFull Auto-On · C405.2.1.4 Dim · LL97 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | Base building corridor: C405.2.1.4 REQUIRED — reduce to ≤50% within 15 min; NOT full off. DIMMING per C405.2.3 item 11. Wired zone control per corridor segment. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 |
Q7 | High-Rise Mechanical / Electrical FloorVacancy Sensor · NEC 110.26(D) · C405.2.1.1 | — | — | ◉§2.1 | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.71C405.3 T.C405.3.2(2) | C405.2.1 item 17: enclosed ≤300 SF — occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3. | 20 fc avg IES HB 10th Ed. |
Q8 | High-Rise Rooftop AmenityOcc Sensor Interior · Astro TC Exterior · LL97 | — | 50§2.1 | — | ⏱§2.2 | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.76C405.3 T.C405.3.2(2) | Rooftop amenity (interior+exterior): Interior zones: C405.2.1 occ sensor. Exterior zones: C405.2.7 timeclock + C405.2.7.3 setback. C405.2.2 time-switch for exterior. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. Tunable white. C408.3. | 10–30 fc avg IES HB 10th Ed. |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
R1 | High-Rise Dwelling UnitManual Only · Residential Exception · Tunable White | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.46C405.3 T.C405.3.2(2) | High-rise dwelling unit: C405.2.10 Exception — MANUAL controls permissible (no occ sensor). DIMMING per C405.2.3. Tunable white for circadian (not code-mandated). Wireless for tenant control. C408.3 for any automated systems. | 5–20 fc avg IES HB 10th Ed. |
R2 | High-Rise Amenity LevelFull Integration · Occ Sensor · AV · LL88 · LL97 | — | 50§2.1 | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | 📽 | ▧ | — | ≋ | — | 0.44C405.3 T.C405.3.2(2) | High-rise amenity level: C405.2.1 occ sensor. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. AV + automated shades for event flex. Tunable white. C405.2.8. C408.3. | 15–30 fc avg IES HB 10th Ed. |
R3 | High-Rise Residential CorridorFull Auto-On · C405.2.1.4 · LL97 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | Residential corridor: C405.2.1.4 — REDUCE TO ≤50% within 15 min; full shutoff NOT permitted. DIMMING per C405.2.3. Wired zone control per floor. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 |
R4 | High-Rise Residential LobbyFull Auto-On · Daylight · LL88 Metered | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | Residential lobby: C405.2.1.1 Exc 1 — full auto-on. DIMMING per C405.2.3 item 8 — REQUIRED (lobbies). DAYLIGHT per C405.2.4. Tunable white. C405.2.8. C408.3. | 20–30 fc avg ANSI/IES RP-1-24 §7 |
R5 | High-Rise Fitness Center / GymOcc Sensor · Tunable White · Daylight · LL97 | — | 50§2.1 | — | — | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.82C405.3 T.C405.3.2(2) | Residential fitness: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 — REQUIRED (gyms/fitness). DAYLIGHT per C405.2.4. Tunable white for workout/recovery. C405.2.8. C408.3. | 30–50 fc workout IES RP-6-15 §5 |
R6 | High-Rise Rooftop TerraceInterior Occ Sensor · Exterior Astro TC · LL97 | — | 50§2.1 | — | ⏱§2.2 | — | ◐§2.3 | — | ⟁ | ☀§2.4 | — | — | — | ≋ | — | N/AExterior C405.2.7 | Rooftop terrace (exterior): C405.2.7 exterior controls. C405.2.7.3: reduce ≥50% at midnight. C405.2.2 time-switch for scheduled events. Interior occ sensor for any enclosed zones. DAYLIGHT per C405.2.4. Tunable white. C408.3. | 2–10 fc avg IES G-1 |
R7 | High-Rise Residential ParkingC405.2.4 Garage Controls · Safety · LL88 | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 0.11C405.3 T.C405.3.2(2) | C405.2.9 residential parking: auto-on + ≥30% reduction per zone ≤3,600 SF. DAYLIGHT per C405.2.9 item 3 at openings. DIMMING per C405.2.3. C408.3. | 5–10 fc avg ANSI/IES RP-10-20 §4 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
OCC SENSOR |
TIME CLOCK |
MAN DIM |
MAN OVRD |
DAY DIM |
OCC EXEMPT |
DIM CTRL |
EMER CIRC |
ASTRO TC |
|||||||
S1 |
Secure Corridor / Housing Unit CorridorCorrectional Facility · C405.2.1.4 Dim-Only · No Full Shutoff | — | 50§2.1 | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | — | — | — | 0.44C405.3 T.C405.3.2(2) |
Secure corridor: C405.2.1.4 — reduce to ≤50%; NEVER full off (security). C405.2.2 time-switch backup. DIMMING per C405.2.3. Security/CCTV integration via wired control only. AV for intercom. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 |
|
S2 |
Inmate Housing Cell / Detention Room<400 SF · C405.2.1 Occ Sensor · Vacancy Preferred | — | — | ◉§2.1 | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | — | — | — | 0.52C405.3 T.C405.3.2(2) |
Detention cell: C405.2.1 item 17 (≤300 SF enclosed). Vacancy sensor. C405.2.2 time-switch. DIMMING per C405.2.3. NOTE: C405.2 Exception 1 — security-critical cells may require manual controls. Security/AV integration. C408.3. | 10–20 fc avg IES HB 10th Ed. |
|
S3 |
Correctional Program Room / Classroom500–3,000 SF · Occ Sensor · Auto-On ≤50% · Dimming Required | — | 50§2.1 | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | — | — | — | 0.74C405.3 T.C405.3.2(2) |
Correctional classroom: C405.2.1 item 1. C405.2.1.1 Exc 2: vacancy required for classrooms. C405.2.2 time-switch. DIMMING per C405.2.3. Security AV integration. C408.3. | 30–50 fc avg ANSI/IES RP-3-20 §4 |
|
S4 |
Psychiatric Ward / Behavioral Health UnitC405.2.1 Occ Sensor · C405.2.1.1 Exception · Patient Safety Controls | ✓§2.1 | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | ▧ | — | — | 0.78C405.3 T.C405.3.2(2) |
Psychiatric ward: C405.2.1 occ sensor. C405.2.1.1 Exc 1: full auto-on (patient safety). C405.2.2 time-switch. DIMMING per C405.2.3 item 5 (healthcare). Automated shades for behavioral therapy. Security AV. C408.3. | 5–20 fc avg ANSI/IES RP-29-25 |
|
S5 |
Correctional Cafeteria / Dining Hall500–5,000 SF · C405.2.1 Occ Sensor · Timeclock if No Sensor | — | 50§2.1 | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | — | — | — | 0.36C405.3 T.C405.3.2(2) |
Correctional cafeteria: C405.2.1 item 6. C405.2.1.3 zone controls ≥300 SF. C405.2.2 time-switch. DIMMING per C405.2.3 item 3. Security AV. C408.3. | 15–25 fc avg IES HB 10th Ed. |
|
S6 |
Institutional Office / Administrative SuitePrison Admin · 500–3,000 SF · Vacancy Sensor · Timeclock | — | — | ◉§2.1 | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | — | — | — | 0.73C405.3 T.C405.3.2(2) |
Institutional office: C405.2.1 item 8 (office). Vacancy. C405.2.2 time-switch. DIMMING per C405.2.3 item 10. Security AV/intercom. C408.3. | 30–50 fc avg ANSI/IES RP-1-24 |
|
S7 |
Exterior Perimeter / Yard Security LightingCorrectional Exterior · C405.2.6 Astro TC · ≥50% Setback Not Always Permitted | — | — | — | ⏱§2.2 | ✋ | — | ⬡ | — | ☀§2.4 | — | ▧ | ⊞§2.1.3 | — | N/AExterior C405.2.7 |
Exterior security perimeter: C405.2.7 exterior controls. C405.2.7.1 daylight auto-off. C405.2.7.3 setback. C405.2 Exception 1: security perimeter — full shutoff may be restricted. Manual override required. C405.2.2 time-switch. Wired security integration. Motion detection. C408.3. | 1–5 fc avg IES G-1 |
|
S8 |
Infirmary / Institutional Medical Room<500 SF · NEC 517 Healthcare Essential Electrical · Auto-On Full | ✓§2.1 | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | — | — | 📽 | ▧ | — | — | 1.16C405.3 T.C405.3.2(2) |
Institutional infirmary: C405.2.1 occ sensor. C405.2.1.1 Exc 1: full auto-on (clinical). C405.2.2 time-switch. DIMMING per C405.2.3 item 5 (healthcare exam). Automated shades. Security + medical integration. C408.3. | 30–75 fc avg IES HB §26 / RP-29 |
|
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
T1 | Hotel / Motel GuestroomC405.2.10 Exception · Manual Controls Permissible · Dimming Required | — | — | — | — | ✋ | ◐§2.3 | — | ⟁ | — | — | — | — | ≋ | — | 0.41C405.3 T.C405.3.2(2) | Hotel/motel guestroom. C405.2.10 Exception — sleeping units may use manual controls (no occ sensor required). C405.2.3 — dimming required. Tunable white for hospitality circadian (not code-mandated). C405.3.3 lamp efficacy requirements apply. Table C405.3.2(2): Guestroom = 0.41 W/SF. C408.3. | 5–30 fc avg IES HB 10th Ed. |
T2 | Hotel Lobby / ReceptionFull Auto-On Permitted · Dimming REQUIRED · C405.2.3 Item 8 | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | ⟁ | ☀§2.4 | — | — | — | ≋ | — | 0.80C405.3 T.C405.3.2(2) | C405.2.1.1 Exception 1 — full auto-on permitted (lobbies). C405.2.3 item 8 — DIMMING REQUIRED for lobbies. C405.2.4 daylight responsive where >75W sidelit. C405.2.8 demand-responsive (Group R-1 ≥10,000 SF). Tunable white for brand identity. Table C405.3.2(2): Lobby otherwise = 0.80 W/SF. C408.3. | 20–50 fc avg ANSI/IES RP-1-24 §7 |
T3 | Hotel Corridor / Guest FloorOcc Sensor Dims to ≤50% — Full Shutoff NOT Permitted · C405.2.1.4 | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.44C405.3 T.C405.3.2(2) | C405.2.1.4 SPECIFIC RULE — occ sensor SHALL reduce to ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED. C405.2.3 dimming required. Wired zone control per floor segment. Table C405.3.2(2): Corridor otherwise = 0.44 W/SF. C408.3. | 5–10 fc avg ANSI/IES RP-28-25 §4 |
T4 | Banquet / Ballroom / Event SpaceTime-Switch REQUIRED · Scene Control · C405.2.5 Special Application | — | — | — | ⏱§2.2 | — | ◐§2.3 | ⬡ | ⟁ | — | 📽 | — | — | ≋ | — | 0.76C405.3 T.C405.3.2(2) | Ballroom/banquet/event space. Not in C405.2.1 mandatory list — C405.2.2 TIME-SWITCH REQUIRED. C405.2.3 item 3 — dimming required (dining). C405.2.5 — theatrical/scene control qualifies as special application. AV integration. Tunable white. Table C405.3.2(2): Dining — bar/lounge/leisure = 0.76 W/SF (2025 NYCECC). C408.3. | 15–30 fc avg Event: 50 fc IES HB 10th Ed. |
T5 | Hotel Fitness CenterOcc Sensor · Dimming REQUIRED · C405.2.3 Item 4 (Gymnasiums) | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | ⟁ | — | — | — | — | ≋ | — | 0.82C405.3 T.C405.3.2(2) | C405.2.1 occ sensor. Auto-on ≤50%. C405.2.3 item 4 — DIMMING REQUIRED (gymnasiums/fitness centers). Tunable white for workout and recovery. C405.2.8 demand-responsive. Table C405.3.2(2): Gymnasium/fitness — exercise area = 0.82 W/SF (2025 NYCECC). C408.3. | 30–50 fc workout IES RP-6-15 §5 |
| ⬡ CODE | SPACE / AREA TYPE | OCCUPANCY CONTROLS | MANUAL CONTROLS | SPECIALTY CONTROLS | PLUG LOAD CONTROL |
MAX LPD W/SF |
CONTROL NARRATIVE · 2025 NYCECC CITATION | IES FC TARGET | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AUTO-ON FULL |
AUTO-ON ≤50% |
VAC SNSR |
TIME CLK |
MAN ONLY |
DIM | WIRED CTL |
WRLS CTL |
DAYLT C405.2.4 |
AV | SHADES | PART | TUN WHITE | PLUG LOAD C405.13 |
|||||
V1 | Vehicular Maintenance / Auto Service BayOcc Sensor · Auto-On ≤50% · Vehicular Maintenance LPD 0.53 W/SF | — | 50§2.1 | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.53C405.3 T.C405.3.2(2) | C405.2.1 occ sensor required. Auto-on ≤50%. C405.2.3 — dimming required. C405.2.8 demand-responsive (Group S ≥10,000 SF). C405.2.5 — task lighting over vehicles may qualify as special application. Table C405.3.2(2): Vehicular maintenance area = 0.53 W/SF. C408.3. | 30–50 fc avg Pit/lift: 50 fc IES HB 10th Ed. |
V2 | Emergency Vehicle Garage / Fire Station BayFull Auto-On Permitted · C405.2.1.1 Exception 1 · Safety Override | ✓§2.1 | — | — | — | — | ◐§2.3 | ⬡ | — | — | — | — | — | — | — | 0.41C405.3 T.C405.3.2(2) | C405.2.1 occ sensor (large enclosed space). C405.2.1.1 Exception 1 — full auto-on permitted (safety environments). C405.2.3 dimming. C405.2 Exception 1 may apply for emergency dispatch bays where auto-shutoff would endanger safety. Table C405.3.2(2): Emergency vehicle garage = 0.41 W/SF. C408.3. | 20–30 fc avg IES HB 10th Ed. |
V3 | Indoor Parking Garage — CommercialC405.2.9 SPECIFIC PARKING CONTROLS · Zone Reduction + Daylight at Openings | ✓§2.1 | — | — | — | — | ◐§2.3 | — | — | ☀§2.4 | — | — | — | — | — | 0.11C405.3 T.C405.3.2(2) | C405.2.9 SPECIFIC PARKING CONTROLS: occ sensor + auto-reduce ≥30% per zone ≤3,600 SF within 15 min. Item 2: vehicle entry eye-adaptation — reduce ≥50% sunset to sunrise. Item 3: within 20 ft of perimeter openings or skylights — auto-reduce ≥50% in response to daylight. C405.2.3 dimming. Table C405.3.2(2): Parking area interior = 0.11 W/SF. C408.3. | 5–10 fc avg ANSI/IES RP-10-20 §4 |
General Notes — 2025 NYCECC
Provide control devices with required power pack, room controller, or other device as shown on plan per manufacturer specifications.
Zoning: provide per light type or as shown on plan; all zones shall have distinct control circuits per C405.2.1.3.
Control stations: coordinate configuration, number, height, and location with ADA requirements per ICC A117.1.
LPD: all spaces shall not exceed max LPD per 2025 NYCECC Table C405.3.2(1). LPD applies to all permanently installed lighting.
NYC LL88: Buildings >25,000 SF — tenant electrical submetering required for each tenant space >5,000 SF. Coordinate with LL88 requirements simultaneously with NYCECC compliance.
NYC LL97: Carbon intensity reporting required. Lighting LPD compliance directly impacts carbon penalty calculations. Class B office: 0.00846 tCO2e/SF by 2030.
⚡ REV 63 — C405.13 AUTO RECEPTACLE CONTROL: Effective with 2025 NYCECC enforcement (March 30, 2026), automatic plug load control is MANDATORY in all offices, conference rooms, and open work areas. At minimum, 50% of 125V, 15A & 20A receptacles in these spaces must be on controlled circuits that auto-de-energize with the occupancy sensor (15-min timeout). Controlled receptacles must be marked with △ per C405.13.1. Provide at least one always-on hot receptacle per workstation. Coordinate controlled receptacle switching with the lighting control panel or a dedicated plug load controller relay output. See note E and C405.13 code modal for full requirements.
Controls Notes — 2025 NYCECC Citations
A. DIMMING — C405.2.3 (2025 NYCECC): MANDATORY for general lighting in: classrooms/lecture halls/training rooms, conference/multipurpose/meeting rooms, dining areas (bar/lounge, leisure, family), gymnasiums/fitness centers, healthcare imaging rooms/exam rooms/nurseries/nurses' stations, laboratories, library reading rooms, lobbies, lounge/break rooms, offices (all), and spaces not provided with occupant sensor controls per C405.2.1.1. Control function (C405.2.3.1): Manual controls shall allow continuous dimming from full output to 10% of full power or lower, plus full off. Manual dimmer control required within each room. Exception: High-end trim controls exempt if calibration accessible only to authorized personnel and users cannot override above trim setpoint. Exception: Luminaires with special application controls per C405.2.5.
B. DAYLIGHT RESPONSIVE CONTROLS — C405.2.4 (2025 NYCECC): MANDATORY when installed general lighting wattage within a daylight zone exceeds the trigger threshold below. Applies to each zone independently — exceeding the threshold in one zone does not require controls in others.
Zone wattage count: Sum rated input wattage of all general lighting luminaires whose photometric center falls within the zone boundary. Task, decorative, and C405.2.5 special application fixtures are excluded. Luminaires straddling the boundary within 2 ft of the perimeter may be counted at 50%.
Control function (C405.2.4.1): Continuous dimming from full output to ≤15% of full rated light output (not wattage) before shutoff. Complete shutoff capability required. Step dimming is not permitted. Independent zone control required: toplit zones separate from sidelit; primary separate from secondary; each cardinal façade orientation separately controlled. Calibration accessible only to authorized personnel. When occupant sensor reduces to unoccupied setpoint, daylight controls continue operating but may not increase power above unoccupied setpoint.
Commissioning (C408.3.1.3): All daylight controls shall be calibrated and functionally tested by an approved agency prior to final inspection. Verification confirms field calibration, ≤15% dim floor, smooth continuous response, and zone independence.
Exceptions: (EX 1) Healthcare spaces where patient care is directly provided — patient rooms, OR, ICU, exam/treatment, nurseries (corridors, lobbies, and offices NOT exempt). (EX 2) Sidelit zones on the ground floor above grade in Group A-2 and M occupancies (toplit zones on ground floor are NOT exempt). (EX 3) Enclosed offices <250 SF.
Design guide: Primary zone depth = window head height (e.g., 9 ft head → 9 ft primary zone; 12 ft head → 12 ft primary, 12–20 ft secondary). Toplit zone radius = 0.7× ceiling height (e.g., 14 ft ceiling → 9.8 ft radius; 28 ft warehouse ceiling → 19.6 ft radius). Raise head heights and use high-VT glazing to maximize daylit area per zone and reduce the number of independently controlled zones.
| Zone Type | Wattage Trigger | Zone Depth (from glazing face) | Glazing Qualification |
|---|---|---|---|
| Primary Sidelit | >75 W | Lesser of: 1× window head height or 15 ft | Vert. glazing ≥24 SF, VT ≥0.20 |
| Secondary Sidelit | >150 W | From primary zone edge to lesser of: 2× head height or 20 ft | Same fenestration as primary |
| Toplit — Skylights | >75 W | 0.7× ceiling height in all directions from skylight edge | Skylight area ≥24 SF per zone |
| Toplit — TDDs | >75 W | 0.7× ceiling height from TDD edge | ≥0.1 SF aperture per device |
C. AV INTEGRATION: Refer to AV integration note on drawings per C405.2.3. Coordinate scene presets with AV contractor. Scene presets must include ≤20% level for AV/presentation mode.
D. MOTORIZED SHADES: Provide fully integrated shade connection with lighting controls system. Coordinate shade position with daylight sensor per C405.2.4. Shade position shall be communicated to the daylight responsive control system so that the photosensor setpoint can be adjusted based on shade deployment state. When shades are fully closed, the daylight control system shall operate from a stored setpoint for overcast/no-daylight conditions. Coordinate shade schedule with WELL Building Standard v2 L04 (Daylight) where applicable.
E. AUTOMATIC RECEPTACLE CONTROL — C405.13 (2025 NYCECC): REV 63 — C405.13 MANDATORY. Automatic receptacle control is required for ≥50% of all 125V, 15A and 20A receptacles in the following space types: enclosed offices, conference rooms, copy/print rooms, breakrooms, classrooms, open plan office areas, and individual workstations (including modular partitions/workstation systems). Additionally, ≥25% of branch circuit feeders installed for modular furniture not shown on construction documents must be controlled.
Control method — one of the following (C405.13.1): (2.1) Timeclock — scheduled time-of-day control, programmable per day, zone ≤5,000 SF and ≤1 floor, 2-hour manual override permitted, override switch controls ≤5,000 SF; (2.2) Occupant sensor — turns off receptacles within 15 minutes of all occupants leaving; (2.3) Automated signal from another control/alarm system — off within 15 minutes of determining unoccupied.
Receptacle configuration (C405.13.1 item 1): Either provide split controlled receptacles with the top receptacle controlled, or provide a controlled receptacle within 12 inches of each uncontrolled receptacle.
Marking (C405.13.1 item 3): All controlled receptacles shall be permanently marked per the NYC Electrical Code and be uniformly distributed throughout the space. Plug-in devices do not comply (C405.13.1 item 4).
Exceptions: (1) Receptacles for continuous operation equipment (24/7/365); (2) Spaces where auto control would endanger safety/security; (3) Within a single modular workstation, uncontrolled receptacles may be >12 in. but ≤72 in. from controlled receptacles.
Control method — one of the following (C405.13.1): (2.1) Timeclock — scheduled time-of-day control, programmable per day, zone ≤5,000 SF and ≤1 floor, 2-hour manual override permitted, override switch controls ≤5,000 SF; (2.2) Occupant sensor — turns off receptacles within 15 minutes of all occupants leaving; (2.3) Automated signal from another control/alarm system — off within 15 minutes of determining unoccupied.
Receptacle configuration (C405.13.1 item 1): Either provide split controlled receptacles with the top receptacle controlled, or provide a controlled receptacle within 12 inches of each uncontrolled receptacle.
Marking (C405.13.1 item 3): All controlled receptacles shall be permanently marked per the NYC Electrical Code and be uniformly distributed throughout the space. Plug-in devices do not comply (C405.13.1 item 4).
Exceptions: (1) Receptacles for continuous operation equipment (24/7/365); (2) Spaces where auto control would endanger safety/security; (3) Within a single modular workstation, uncontrolled receptacles may be >12 in. but ≤72 in. from controlled receptacles.
F. PARTITION SENSOR: Rooms act independently when partition in place; zones unify when partition removed. Each partition zone separately zoned per C405.2.1.3.
G. TUNABLE WHITE: Tunable white controls with circadian programming per IES TM-18. CCT range 2700K–6500K. Coordinate with WELL Building Standard v2 L07.
H. DEMAND RESPONSIVE LIGHTING CONTROLS — C405.2.8 (2025 NYCECC): MANDATORY for interior general lighting in Group B (Business), E (Educational), M (Mercantile), and S (Storage) occupancies — covering not less than 75% of interior floor area. Upon receipt of a utility/grid demand response (DR) signal: (1) Reduce lighting output to ≤80% of full power (or ≤80% of high-end trim setpoint if trim is set); (2) Dim gradually and continuously over not more than 15 minutes to achieve the DR setpoint; (3) Automatically restore to normal settings after the DR event ends. Exceptions (C405.2.8): Buildings <10,000 SF total Group B/E/M/S area; buildings where DR signal is not available from a controlling entity other than the owner; parking garages; ambulatory care facilities; outpatient clinics; physician or dental offices. Warehouse/storage areas exception: may switch off ≥25% of general lighting power rather than dimming. Coordination required with utility/grid aggregator for DR signal protocol (typically OpenADR 2.0 or BACnet). Commissioning per C408.3.1.6 required for buildings claiming C406.3.2 credits.
I. COMMISSIONING — C408.3 FUNCTIONAL TESTING (2025 NYCECC): MANDATORY per C405.1: Lighting controls shall be commissioned per C408.3 prior to passing final inspection. An approved agency shall provide evidence that all lighting and receptacle control systems have been tested to ensure control hardware and software are calibrated, adjusted, programmed, and in proper working condition. Testing protocols: Occupant sensors (C408.3.1.1): ≤7 sensors → test all; >7 → test ≥10% of each unique type/geometry; ≥30% fail → test all; verify auto-off timing, on-level, manual-on behavior, and no cross-zone false triggering. Time-switch controls (C408.3.1.2): Confirm programming (weekday/weekend/holiday), correct time/date, battery backup, and ≤2-hr override limit; simulate occupied and unoccupied conditions. Daylight controls (C408.3.1.3): Verify field calibration, setpoints, and response to available daylight. High-end trim (C408.3.1.4): Verify trim set, calibration secured, users cannot override above trim max. Documentation due within 90 days of CO (C408.3.2): Equipment location drawings, O&M manuals (setpoints, service contacts, maintenance schedules, recalibration schedule), and test results report with deficiency disposition.
2025 NYCECC Code Citations — Quick Reference
C405.2.1 OCCUPANT SENSOR CONTROLS: Required in 18 space types: (1) classrooms/lecture/training, (2) computer rooms/data centers, (3) conference/meeting/multipurpose, (4) copy/print rooms, (5) lounges/breakrooms, (6) cafeteria & fast food dining, (7) medical supply rooms (healthcare), (8) enclosed offices, (9) laundry/washing areas, (10) open plan offices, (11) restrooms, (12) storage rooms, (13) telemedicine rooms (healthcare), (14) locker rooms, (15) corridors/transition areas/stairways, (16) warehouse storage areas, (17) other spaces ≤300 SF enclosed by floor-to-ceiling partitions, (18) janitorial closets. Control function varies by space type — see C405.2.1.1 through C405.2.1.5. C405.2.1.1: Auto-on to ≤50% for standard spaces. Full 100% auto-on ONLY for: corridors, stairways, restrooms, primary entrances, lobbies, safety spaces.
C405.2.1.2: WAREHOUSE RULE — auto-on to FULL power; reduce ≥50% when unoccupied. NOT the standard ≤50% auto-on rule.
C405.2.1.3: Open office ≥300 SF — zones ≤600 SF. Occupied zone full. Adjacent vacant zones ≤20%. Full space ≤20% after all zones vacant.
C405.2.1.4: CORRIDOR DIM — reduce to ≤50%; FULL OFF NOT PERMITTED. Egress min. 1.0 fc at floor level must be maintained at all times.
C405.2.2 TIME-SWITCH CONTROLS: Required in areas NOT provided with occupant sensor controls per C405.2.1.1. Exceptions: (1) luminaires requiring specific application controls per C405.2.4; (2) spaces where patient care is directly provided. Function (C405.2.2.1): 7-day programmable clock; 7 day-types per week; automatic holiday shutoff (≥24 hr, then resumes normal); program backup ≥10 hr if power interrupted; manual override switch permits lighting on for ≤2 hr at a time, controlling area ≤5,000 SF; for unscheduled spaces — default programmed to turn off lights ≥12 hr/day. Mall/auditorium/sales/manufacturing/arena exception: override may exceed 2 hr (captive key) and area may exceed 5,000 SF (but <20,000 SF).
C405.2.3 DIMMING: Continuous dimming REQUIRED for general lighting in classrooms, conference rooms, dining, gymnasiums, healthcare, laboratories, libraries, lobbies, lounge/breakrooms, and all offices. Manual dimmer shall allow continuous dim from full output to ≤10% power plus full off. Step dimming is not permitted. One manual dimmer control per room or zone.
C405.2.4 DAYLIGHT CONTROLS: Wattage thresholds: Primary sidelit zone >75W trigger; Secondary sidelit >150W; Toplit (skylights/TDDs) >75W. Zone geometry: primary = 1× head height or 15 ft (lesser); secondary = 1–2× head height or 15–20 ft; toplit = 0.7× ceiling height radius. Qualifications: fenestration ≥24 SF, VT ≥0.20 (sidelit); skylight ≥24 SF (toplit). Control: continuous dim to ≤15% before shutoff; toplit, primary, secondary, and each cardinal orientation independently controlled. Commissioning: C408.3.1.3 required. See modal and Note B for full requirements.
C405.2.6: Exterior — astronomical timeclock REQUIRED. Daylig