⚠ Key Requirements
Enterprise Lighting Sales · 2025 NYCECC

2025 NYCECC Compliance
Reference

Revision116-BF
Code Year2025 NYCECC
EnforcementMarch 30, 2026
AuthorityNYC DOB
LPD RefC405.3 · Table C405.3.2(1)
Controls RefC405.2 · C405.13
CommissioningC408.3
135
Space Types
135 Space Types — click to filter table
21
Categories
21 Categories — click to filter table
ALL All CategoriesShow all 135 space types
ACommercial Offices11 space types
BResidential Buildings3 space types
CLobbies & Amenity3 space types
DCorridors & Stairways3 space types
EExterior Lighting3 space types
FRetail5 space types
GFood Service5 space types
HHealthcare — General/Clinical13 space types
IOR / Procedure & Sterile3 space types
JEducation — K-1211 space types
KUniversities & Higher Ed9 space types
LPublic & Civic8 space types
MParking6 space types
NWarehouse & Industrial5 space types
OData Centers3 space types
PSupport & Utility13 space types
QHigh-Rise Office (>75 ft)8 space types
RHigh-Rise Residential (>75 ft)7 space types
SCorrectional & Secure5 space types
TTransit & Transportation5 space types
18
Code Sections
18 Code Sections — click to filter table
ALL All Code SectionsClear code filter
2.1C405.2.1 — Occupant Sensor Controls18 mandatory space types · 112 spaces
2.1.1C405.2.1.1 — Auto-On ≤50% / VacancyStandard auto-on & manual-on rules · 83 spaces
2.1.2C405.2.1.2 — Warehouse AislewayFull auto-on; reduce ≥50% vacant · 3 spaces
2.1.3C405.2.1.3 — Open Office Zone ControlZones ≤600 SF; adjacent ≤20% · 10 spaces
2.1.4C405.2.1.4 — Corridor Dim-to-50%No full shutoff; egress 1.0 fc min · 8 spaces
2.2C405.2.2 — Time-Switch Controls7-day clock; 2-hr override; ≤5,000 SF · 20 spaces
2.3C405.2.3 — Dimming to ≤10%Continuous; no step dimming · 128 spaces
2.4C405.2.4 — Daylight Responsive>75W sidelit / >150W secondary / >75W toplit · 41 spaces
2.5C405.2.5 — Specific Application ControlsDisplay, task, AV-integrated lighting
2.8C405.2.8 — Demand ResponsiveGroup B/E/M/S ≥10K SF; reduce to ≤80% · 82 spaces
2.9C405.2.9 — Interior Parking Controls≤3,600 SF zones; 30% setback · 6 spaces
405.3C405.3 — Interior LPDTable C405.3.2(2) space-by-space · all spaces
405.13C405.13 — Auto Receptacle Control⚡ ≥50% of 125V, 15/20A recepts · 21 spaces
408.3C408.3 — Functional TestingMandatory before final inspection · all 135 spaces
NEC700NEC Art. 700 — Emergency CircuitsExempt from energy controls · 3 spaces
NEC517NEC Art. 517 — Healthcare Essential Elec.Life-safety branch; no energy controls · 5 spaces
Symbol Key AUTO-ON 100% — Safety/Lobby Exception C405.2.1.1 AUTO-ON ≤50% — Standard Occ Sensor C405.2.1.1 MANUAL-ON / 15-Min Auto-Off — Vacancy Sensor TIMECLOCK — When No Occ Sensor C405.2.2 DAYLIGHT DIMMING Required C405.2.4 WIRELESS Manual Controls PLUG LOAD — Auto Receptacle Control Required C405.13 Not Applicable
A
COMMERCIAL OFFICES
Occupancy sensors REQUIRED in all enclosed offices, open offices, conference rooms, break rooms per C405.2.1. Timeclock required ONLY when no occ sensor provided per C405.2.2. Dimming required per C405.2.3. ⚡ C405.13 PLUG LOAD CONTROL REQUIRED — all spaces in this category.
11 SPACE TYPES
◆ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
A1
Commercial Private OfficeVacancy Sensor · Manual-On · Auto-Off 15 min · C405.2.1.1§2.1§2.3🔌§405.130.73C405.3
T.C405.3.2(2)
VACANCY SENSOR REQUIRED per C405.2.1 (item 8: enclosed offices) + C405.2.1.1: manual-on, auto-off within 15 min. DIMMING REQUIRED per C405.2.3 item 10 (offices). AUTO RECEPTACLE per C405.13 item 1.1 — ≥50% of 125V outlets. DEMAND RESPONSIVE per C405.2.8 if bldg Group B ≥10,000 SF. C408.3: commissioning required.30–50 fc avg
ANSI/IES RP-1-24 §4.1
A2
Commercial Private OfficeVacancy Sensor · Manual-On · Auto-Off 15 min§2.1§2.3🔌§405.130.73C405.3
T.C405.3.2(2)
VACANCY SENSOR per C405.2.1.1: manual-on, auto-off ≤15 min, manual off switch required. DIMMING per C405.2.3 item 10: 100%→10% continuous. PLUG LOAD per C405.13 item 1.1. C408.3: all controls commissioned.30–50 fc avg
ANSI/IES RP-1-24 §4.1
A3
Commercial Private OfficeAuto-On ≤50% · Occ Sensor50§2.1§2.3🔌§405.130.73C405.3
T.C405.3.2(2)
AUTO-ON ≤50% per C405.2.1.1 Exception 1 — full auto-on ≤50% power permitted in lieu of manual-on. Auto-off ≤15 min. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 item 1.1. C405.2.8: demand-responsive where bldg Group B ≥10,000 SF.30–50 fc avg
ANSI/IES RP-1-24 §4.1
A4
Private Office · Daylight + VacancyPerimeter Office · C405.2.3 Daylight§2.1§2.3§2.4🔌§405.130.73C405.3
T.C405.3.2(2)
VACANCY + DAYLIGHT per C405.2.1.1 + C405.2.4: daylight responsive REQUIRED if >75W in primary sidelit zone. DIMMING per C405.2.3 item 10. Automated shades integrate with daylight sensor. PLUG LOAD per C405.13 item 1.1. C408.3.30–50 fc avg
Perim: 50 fc
ANSI/IES RP-1-24 §4.1
A5
Open Office ≤300 SFVacancy Sensor · C405.2.1.3 Not Required§2.1§2.3🔌§405.130.56C405.3
T.C405.3.2(2)
Open office ≤300 SF: VACANCY SENSOR per C405.2.1 item 17 (enclosed ≤300 SF) + C405.2.1.1: manual-on, auto-off. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 items 1.6–1.7. C405.2.8 demand-responsive.30–50 fc avg
ANSI/IES RP-1-24 §4.2
A6
Open Office ≥300 SFZone Controls REQUIRED — C405.2.1.350§2.1§2.3§2.1.3🔌§405.130.56C405.3
T.C405.3.2(2)
Open plan ≥300 SF: C405.2.1.3 REQUIRED — zone controls ≤600 SF each; unoccupied zones auto-on ≤20%; auto-off all zones ≤15 min. PARTITION SENSORS per zone. AUTO-ON ≤50% within zone. DIMMING per C405.2.3 item 10. PLUG LOAD per C405.13 items 1.6–1.7. C405.2.8.25–40 fc avg
ANSI/IES RP-1-24 §4.2
A7
Conference / Meeting RoomVacancy Sensor REQUIRED · AV Integration§2.1§2.3🔌§405.130.88C405.3
T.C405.3.2(2)
Conference/meeting room: C405.2.1 item 3 requires occ sensor. C405.2.1.1 Exception 2: VACANCY (manual-on) SPECIFICALLY REQUIRED — full auto-on NOT permitted for conference rooms. DIMMING per C405.2.3 item 2. PLUG LOAD per C405.13 item 1.2.30–50 fc avg
ANSI/IES RP-1-24 §5
A8
Open Office · Full IntegrationDaylight + AV + Tunable White · C405.2.1.350§2.1§2.3§2.4§2.1.3🔌§405.130.56C405.3
T.C405.3.2(2)
Open office full integration: C405.2.1.3 zone controls + auto-on ≤20%. DAYLIGHT per C405.2.4 (>75W sidelit). DIMMING per C405.2.3. Tunable white (circadian/wellness, not code-mandated). PARTITION sensors. PLUG LOAD per C405.13. C405.2.8.25–40 fc avg
ANSI/IES RP-1-24 §4.2
A9
Conference · Full IntegrationDaylight + AV + Shades + Tunable White§2.1§2.3§2.4📽🔌§405.130.88C405.3
T.C405.3.2(2)
Conference full integration: C405.2.1.1 Exc 2: VACANCY required. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 2. AV per C405.2.5 special application. Tunable white. PLUG LOAD per C405.13 item 1.2. C408.3.30–50 fc avg
AV dim: 5–10 fc
ANSI/IES RP-1-24 §5
A10
Break Room / Pantry / LoungeVacancy Sensor REQUIRED · Manual-On Only§2.1§2.3🔌§405.130.55C405.3
T.C405.3.2(2)
C405.2.1 item 5: BREAKROOMS require occ sensor. C405.2.1.1 Exc 2: manual-on/vacancy required. DIMMING per C405.2.3 item 9 (lounge/break rooms). PLUG LOAD per C405.13 item 1.4 (breakrooms). C405.2.8 demand-responsive.10–30 fc avg
IES HB 10th Ed.
A11
Reception / Front of HousePrimary Entrance · Full Auto-On Permitted§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
Reception/lobby-type: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies). DIMMING per C405.2.3 item 8 (lobbies). DAYLIGHT per C405.2.4 if >75W sidelit. Tunable white (not code-mandated). C405.2.8 demand-responsive. C408.3.20–30 fc avg
IES HB 10th Ed.
B
RESIDENTIAL BUILDINGS
Dwelling units EXEMPT from occ sensors (C405.2.1) and timeclocks (C405.2.2) — residential exception applies. Common areas require full C405.2 compliance.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
B1
Residential Dwelling UnitLiving / Bedroom · Manual Only§2.30.46C405.3
T.C405.3.2(2)
Dwelling unit: C405.2.10 Exception — dwelling units may use MANUAL controls (no occ sensor required). DIMMING per C405.2.3 still required. Wireless per tenant preference. C408.3: commissioning for any automated controls installed.5–20 fc avg
IES HB 10th Ed.
B2
Residential Dwelling UnitTunable White · Circadian · Manual Only§2.30.46C405.3
T.C405.3.2(2)
Dwelling unit — tunable white: C405.2.10 Exception — manual controls. DIMMING per C405.2.3. Tunable white for circadian wellness (not code-mandated, voluntary). Wireless control. C408.3.5–20 fc avg
IES HB 10th Ed.
B3
Residential Common Area / AmenityFull Auto-On · Safety Exception · C405.2.1.1§2.1§2.3§2.40.44C405.3
T.C405.3.2(2)
Residential common area: C405.2.1 occ sensor required (corridors/common). C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. DAYLIGHT per C405.2.4 if applicable. C408.3.10–20 fc avg
IES HB 10th Ed.
C
LOBBIES & AMENITY SPACES
Primary entrance lobbies: full auto-on per C405.2.1.1 Exception. Amenity spaces: occ sensor auto-on ≤50%. Multi-use spaces: zones ≤600 SF per C405.2.1.3 if ≥300 SF.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
C1
Building Lobby · Primary EntranceFull Auto-On · C405.2.1.1 Exception§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
Building lobby: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies explicitly listed). DIMMING per C405.2.3 item 8 — REQUIRED for lobbies. DAYLIGHT per C405.2.4. C405.2.8 demand-responsive. Tunable white (not code-mandated). C408.3.20–30 fc avg
ANSI/IES RP-1-24 §7
C2
Amenity Space · Fitness / Club RoomOcc Sensor · AV · Tunable White50§2.1§2.3§2.4📽0.82C405.3
T.C405.3.2(2)
Amenity/fitness center: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 4 — REQUIRED for gymnasiums/fitness centers. DAYLIGHT per C405.2.4. AV for programming. Tunable white. C405.2.8.30–50 fc workout
IES RP-6-15 §5
C3
Multi-Use Amenity · Flex SpacePartition Sensor · AV · Daylight · Shades50§2.1§2.3§2.4📽§2.1.30.88C405.3
T.C405.3.2(2)
Multi-use flex space: C405.2.1.3 zone controls per partition zone ≤600 SF. DIMMING per C405.2.3 item 2 (multipurpose). DAYLIGHT per C405.2.4. Automated shades + AV + partition sensors. C405.2.8. C408.3.20–50 fc avg
ANSI/IES RP-1-24 §5
D
CORRIDORS & STAIRWAYS
C405.2.1.4: Corridors dim to ≤50% on vacancy — FULL OFF NOT PERMITTED (egress min. 1.0 fc required at all times). Interior exit stairways exempt from C405.2 automatic controls. Emergency egress on NEC 700 — NOT subject to NYCECC energy controls.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
D1
Corridor / Transition AreaOcc Sensor Dims to ≤50% — Full Shutoff NOT Permitted · C405.2.1.450§2.1§2.30.44C405.3
T.C405.3.2(2)
Corridor: C405.2.1.4 SPECIFIC RULE — occ sensor SHALL reduce to ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED. Exception: corridors <2 fc at darkest point exempt. DIMMING per C405.2.3 (space without C405.2.1.1 → item 11 applies). Wired zone control per segment. C408.3.5–10 fc avg
ANSI/IES RP-28-25 §4
D2
Stairway / Interior Exit StairStairway · Full Auto-On Permitted · C405.2.1.1 Exception 1§2.1§2.30.47C405.3
T.C405.3.2(2)
Interior stairway (non-exit): C405.2.1 item 15 — stairways require occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted (stairways). DIMMING per C405.2.3. NOTE: Interior EXIT stairways EXEMPT per C405.2 Exception 2. C408.3.5–10 fc avg
NFPA 101 §7.9
D3
Emergency Egress / Exit Path LightingEmergency Egress · EXEMPT from C405.2 Auto Controls · NEC 700N/ANEC 700
Not in LPD
Emergency egress/exit path lighting. C405.2 Exception 2 — INTERIOR EXIT STAIRWAYS, RAMPS and PASSAGEWAYS are EXEMPT from C405.2.1 automatic controls. C405.2 Exception 3 — emergency lighting that is auto-off during normal operations is exempt. NEC Article 700 governs. Manual controls only. No dimming required.1 fc min path
NFPA 101 §7.9
E
EXTERIOR LIGHTING
Astronomical timeclock REQUIRED for ALL exterior lighting per C405.2.6 — automatic daylight shutoff and scheduled operation mandatory. Setback ≥50% during unoccupied periods per C405.2.6.2. Curfew shutoff per C405.2.6.3.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
E1
Exterior Entry / Walkway / PlazaAstronomical Timeclock REQUIRED · C405.2.6§2.2§2.4N/AExterior
C405.2.7
Exterior entry/walkway: C405.2.7.1 — lights AUTO-OFF when daylight satisfies need. C405.2.7.3 — reduce ≥50% at midnight or 1hr after close or 15-min inactivity. Astronomical timeclock required. No occ sensor required for exterior. C408.3.2–5 fc avg
ANSI/IES RP-8-25 §5
E2
Exterior Parking Lot / Surface LotAstronomical Timeclock REQUIRED · ≥50% Setback§2.2§2.4N/AExterior
C405.2.7
Exterior parking lot: C405.2.7.1 daylight auto-off. C405.2.7.3: luminaires >40W at ≤24 ft mounting — reduce ≥50% when no activity for 15 min. Astronomical timeclock for dusk-to-dawn. C408.3.2–5 fc avg
ANSI/IES RP-8-25 §6
E3
Exterior Facade / ArchitecturalAstronomical Timeclock · Curfew Shutoff Required§2.2N/AExterior
C405.2.7
Exterior facade/architectural: C405.2.7.2 SPECIFIC — facade lighting SHALL auto-off when daylight adequate OR not later than 1hr after building close. For 24-hr buildings: off at midnight. NYC Zone 3/4 exception for special events at commissioner discretion. Timeclock required.0.5–3 fc avg
IES G-1
F
RETAIL
Fitting rooms REQUIRED on vacancy sensor per C405.2.1 mandatory list. Display lighting on separate circuits from general. Daylight zones separately controlled per C405.2.3.
5 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
F1
Retail Sales FloorVacancy Sensor · Dimming · Daylight§2.1§2.30.85C405.3
T.C405.3.2(2)
Retail sales floor: C405.2.1 item 17 — spaces ≤300 SF enclosed require occ sensor. Larger retail: C405.2.2 time-switch required if no occ sensor. VACANCY sensor shown. DIMMING per C405.2.3 item 11 (spaces without C405.2.1.1). C405.2.8 demand-responsive if Group M ≥10,000 SF.30–50 fc avg
IES RP-2-20 §4
F2
Retail Sales Floor · DaylitVacancy Sensor + Continuous Daylight Dim§2.1§2.3§2.40.85C405.3
T.C405.3.2(2)
Retail — daylit: VACANCY sensor. DAYLIGHT per C405.2.4 REQUIRED where >75W in sidelit/toplit zone. C402.5.2.2: skylight haze factor >90% for retail. DIMMING per C405.2.3. C405.2.8 demand-responsive. C408.3.30–50 fc avg
IES RP-2-20 §4
F3
Retail Fitting RoomVacancy Sensor REQUIRED · Tunable White§2.1§2.30.45C405.3
T.C405.3.2(2)
Retail fitting room: C405.2.1 item 17 — enclosed ≤300 SF requires occ sensor. C405.2.1.1 Exc 2: manual-on/vacancy required (enclosed ≤300 SF). DIMMING per C405.2.3. C408.3.30–50 fc avg
IES RP-2-20 §5
F4
Retail — Hair / Nail SalonVacancy Sensor · High-Task Illumination · Retail LPD§2.1§2.30.75C405.3
T.C405.3.2(2)
C405.2.1 item 17 (≤300 SF) or sales-floor occ sensor. Vacancy sensor. C405.2.3 — dimming required. Tunable white highly recommended for color accuracy (CRI ≥90, 3500–4000K). Table C405.3.2(2): hair salon 0.65 W/SF, nail salon 0.75 W/SF — use higher. C405.2.8 demand-responsive. C408.3.50–75 fc avg
Station: 75 fc
IES RP-2-20 §5
F5
Retail — Mall ConcourseTime-Switch REQUIRED · Dimming · C405.2.2§2.2§2.30.57C405.3
T.C405.3.2(2)
Mall concourse — common circulation. Not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required (spaces without C405.2.1.1). C405.2.8 demand-responsive (Group M ≥10,000 SF). Table C405.3.2(2): mall concourse 0.57 W/SF. C408.3.20–30 fc avg
IES RP-2-20 §4
G
FOOD SERVICE
Kitchen hoods in continuous operation may qualify for C405.2.2 Exception item 4 for task lighting only — consult DOB plan examiner. High CRI ≥90 required for food safety inspection spaces.
5 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
G1
Restaurant / Dining RoomManual Scene Control · Timeclock Required§2.2§2.30.76C405.3
T.C405.3.2(2)
Restaurant — leisure dining: C405.2.1 does NOT list leisure dining → C405.2.2 TIME-SWITCH REQUIRED (7-day clock, holiday shutoff, 2-hr override max). DIMMING per C405.2.3 item 3 — REQUIRED for dining areas (bar/lounge, leisure, family). C405.2.8 demand-responsive. C408.3.15–30 fc avg
IES HB 10th Ed.
G2
Commercial Kitchen / Prep AreaOcc Sensor · Auto-On ≤50% · High CRI50§2.1§2.31.19C405.3
T.C405.3.2(2)
Commercial kitchen: C405.2.1 occ sensor (food prep/enclosed workspace). Auto-on ≤50%. DIMMING per C405.2.3. C405.2.5 Exception: permanently installed task lighting over equipment exempt from specific app controls. C405.2.8.50 fc avg
IES HB 10th Ed.
G3
Bar / Counter Service AreaVacancy Sensor · Manual Dim · Timeclock§2.1§2.30.76C405.3
T.C405.3.2(2)
Bar/counter service: C405.2.3 item 3 — DIMMING REQUIRED for bar/lounge dining areas. C405.2.1 occ sensor (lounge). Vacancy sensor. C405.2.8 demand-responsive. Wired + wireless for scene management. C408.3.15–30 fc avg
IES HB 10th Ed.
G4
Family Dining RoomTime-Switch REQUIRED · Dimming REQUIRED · C405.2.3 Item 3§2.2§2.30.52C405.3
T.C405.3.2(2)
Family dining room. C405.2.1 does NOT list family dining → C405.2.2 TIME-SWITCH REQUIRED. C405.2.3 item 3 — DIMMING REQUIRED for dining areas (family dining listed). Scene control via time-switch + dimming presets. Table C405.3.2(2): dining area — family 0.52 W/SF. C408.3.15–30 fc avg
IES HB 10th Ed.
G5
Cafeteria / Fast Food DiningOcc Sensor REQUIRED · Zone Controls ≥300 SF · C405.2.1.350§2.1§2.3📽0.36C405.3
T.C405.3.2(2)
C405.2.1 item 6 — cafeteria and fast-food dining REQUIRE occ sensor. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF; auto-on ≤20% unoccupied zones. C405.2.3 item 3 — dimming required (cafeteria). AV for programming. C405.2.8 demand-responsive. Table C405.3.2(2): dining — cafeteria/fast food 0.36 W/SF. C408.3.20–30 fc avg
IES HB 10th Ed.
H
HEALTHCARE — GENERAL / CLINICAL
Patient care spaces EXEMPT from occ sensor per C405.2.1.1 Exception 1 (auto-shutoff endangers patient safety). Patient care EXEMPT from timeclock per C405.2.2 Exception. High CRI ≥90 required for all clinical assessment spaces.
13 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
H1
Patient Room · General / Med-SurgManual Only · Patient Safety Exception§2.30.78C405.3
T.C405.3.2(2)
Patient room: C405.2 Exception 1 — auto-shutoff could endanger patient safety → MANUAL controls acceptable. C405.2.2 Exception 2 — patient care spaces exempt from time-switch. DIMMING per C405.2.3 item 5 — REQUIRED (healthcare patient rooms). Tunable white for circadian. C408.3.5 fc rest / 30 fc exam
ANSI/IES RP-29-25 §5
H2
Patient Room · Perimeter DaylightManual + Daylight + Shades + Tunable White§2.3§2.40.78C405.3
T.C405.3.2(2)
Patient room — daylit: C405.2 Exception 1 — manual controls. DIMMING per C405.2.3 item 5. DAYLIGHT per C405.2.4 — REQUIRED (>75W sidelit). Note: C405.2.4 Exception 1 exempts patient CARE areas — lobbies/daylit rooms w/o care not exempt. Automated shades. Tunable white.5 fc rest / 30 fc exam
ANSI/IES RP-29-25 §5
H3
ICU / Critical Care RoomPatient Safety Exception · Multi-Scene · Tunable White§2.30.78C405.3
T.C405.3.2(2)
ICU/critical care: C405.2 Exception 1 — MANUAL CONTROLS REQUIRED (auto-shutoff endangers critical patient safety). C405.2.2 Exception 2: exempt from time-switch. DIMMING per C405.2.3 item 5. Tunable white for circadian/staff workflow. C408.3.5 fc rest / 50 fc exam
ANSI/IES RP-29-25 §7
H4
Exam Room / Consultation RoomVacancy Sensor · Patient Privacy · High CRI§2.1§2.31.33C405.3
T.C405.3.2(2)
Exam/consultation room: C405.2.1 item 17 (≤300 SF enclosed) — occ sensor. C405.2.1.1 Exc 2: VACANCY required. DIMMING per C405.2.3 item 5 — REQUIRED (exam rooms). C405.2.4 Exception 1: daylight controls EXEMPT for direct patient care. C408.3.50–75 fc avg
ANSI/IES RP-29-25 §6
H5
Telemedicine / Virtual Care RoomVacancy Sensor · Tunable White · High CRI§2.1§2.31.44C405.3
T.C405.3.2(2)
Telemedicine room: C405.2.1 item 13 — SPECIFICALLY LISTED: telemedicine rooms in healthcare REQUIRE occ sensor. C405.2.1.1 Exc 2: vacancy. DIMMING per C405.2.3 item 5. Tunable white for camera color accuracy. C408.3.50–75 fc avg
ANSI/IES RP-29-25 §6
H6
Nursing Station / Care Team HubOcc Sensor · Tunable White · Daylight50§2.1§2.3§2.41.07C405.3
T.C405.3.2(2)
Nursing station: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 5 — REQUIRED (nurses' stations specifically listed). C405.2.4 Exception 1: daylight exempt for patient care. Tunable white for shift-work circadian. C408.3.30–50 fc avg
ANSI/IES RP-29-25 §7
H7
Pharmacy / Medication PreparationOcc Sensor · High CRI ≥90 Mandatory50§2.1§2.31.59C405.3
T.C405.3.2(2)
Pharmacy: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 5 (healthcare). C405.2.4 Exception 1: daylight exempt for patient care. Wired control for precision task lighting. C408.3.50 fc avg
ANSI/IES RP-29-25 §10
H8
Healthcare CorridorFull Auto-On · Dim to ≤50% · C405.2.1.450§2.1§2.30.61C405.3
T.C405.3.2(2)
Healthcare corridor: C405.2.1.4 — REDUCE TO ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED (patient safety). DIMMING per C405.2.3 item 11. Wired zone control per corridor segment. C405.2.8. C408.3.5–10 fc avg
ANSI/IES RP-29-25 §4
H9
Healthcare Lobby / WaitingFull Auto-On · Tunable White · Daylight§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
Healthcare lobby: C405.2.1.1 Exc 1 — full auto-on permitted (lobbies). DIMMING per C405.2.3 item 8 — REQUIRED. C405.2.4: daylight responsive — lobby is NOT direct patient care so Exception 1 does NOT apply here. Tunable white for wellness. C408.3.15–30 fc avg
ANSI/IES RP-29-25 §4
H10
Medical Supply / Storage RoomVacancy Sensor REQUIRED · High CRI§2.1§2.30.54C405.3
T.C405.3.2(2)
C405.2.1 item 7 — SPECIFICALLY LISTED: medical supply rooms in healthcare REQUIRE occ sensor. C405.2.1.1: vacancy sensor (manual-on, auto-off ≤15 min). DIMMING per C405.2.3. C408.3.30 fc avg
ANSI/IES RP-29-25 §8
H11
Nursing Home / LTC Resident RoomPatient Safety Exception · Tunable White§2.30.78C405.3
T.C405.3.2(2)
LTC/nursing home resident room: C405.2 Exception 1 — resident safety, manual controls. C405.2.3 dimming required. C405.2.10 residential exception may also apply. Tunable white for circadian/dementia care (not code-mandated). C408.3.5 fc rest / 20 fc task
ANSI/IES RP-29-25 §5
H12
Senior / Assisted Living UnitResidential Exception · Tunable White§2.30.78C405.3
T.C405.3.2(2)
Senior/assisted living: C405.2 Exception 1 + C405.2.10 residential exception — manual controls. DIMMING per C405.2.3. Tunable white for circadian health (not code-mandated). C408.3.5 fc rest / 20 fc task
ANSI/IES RP-29-25 §5
H13
Rehabilitation / Therapy AreaVacancy Sensor · Patient Privacy · Daylight§2.1§2.30.82C405.3
T.C405.3.2(2)
Rehab/physical therapy: C405.2.1 occ sensor. Vacancy sensor. DIMMING per C405.2.3 item 5 — REQUIRED (physical therapy rooms listed). C405.2.4 Exception 1: daylight exempt for direct patient care. C408.3.30–50 fc avg
ANSI/IES RP-29-25 §9
I
OR / PROCEDURE & STERILE PROCESSING
Operating and procedure rooms EXEMPT from all automatic controls — auto-shutoff during surgical procedures is life-threatening. C405.2.1.1 and C405.2.2 exceptions both apply. Manual scene control only.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
I1
Operating Room / Procedure RoomPatient Safety Exception · Manual Scene Control§2.32.26C405.3
T.C405.3.2(2)
Operating room: C405.2 Exception 1 — MANUAL CONTROLS REQUIRED (auto-shutoff endangers patient life safety). C405.2.2 Exception 2: exempt from time-switch (direct patient care). DIMMING per C405.2.3 item 5 (imaging/procedure). No occ sensor. C408.3.100–200 fc field / 5 fc rest
ANSI/IES RP-29-25 §12
I2
Endoscopy / Interventional SuitePatient Safety Exception · Manual Scene Control§2.32.26C405.3
T.C405.3.2(2)
Endoscopy/interventional suite: C405.2 Exception 1 — manual controls only. C405.2.2 Exception 2. DIMMING per C405.2.3 item 5. Wired precision dimming for procedure visualization. C408.3.75–150 fc avg
ANSI/IES RP-29-25 §12
I3
Sterile Processing / CSPDOcc Sensor · Auto-On ≤50% · High CRI ≥9050§2.1§2.31.19C405.3
T.C405.3.2(2)
Sterile processing/CSPD: not direct patient care — occ sensor required. C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3. Wired control for task zone management. C408.3.50 fc avg
ANSI/IES RP-29-25 §11
J
EDUCATION — K-12
Classrooms REQUIRED on vacancy sensor per C405.2.1 mandatory list. Shop classrooms: timeclock not required per C405.2.2 exception. Natatoriums: full auto-on safety exception.
11 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
J1
Classroom — Standard K-12Vacancy Sensor REQUIRED — C405.2.1 Mandatory List§2.1§2.3🔌§405.130.72C405.3
T.C405.3.2(2)
C405.2.1 item 1 — classrooms REQUIRE occ sensor. C405.2.1.1 Exception 2 — VACANCY (manual-on) SPECIFICALLY REQUIRED for classrooms (full auto-on not permitted). DIMMING per C405.2.3 item 1 — REQUIRED. C405.13 item 1.5 — auto receptacle required. C405.2.8 demand-responsive.30–50 fc avg
ANSI/IES RP-3-20 §4
J2
Classroom · Daylit — K-12Vacancy Sensor + Continuous Daylight Dim · C405.2.3§2.1§2.3§2.4🔌§405.130.72C405.3
T.C405.3.2(2)
Classroom — daylit: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4 — REQUIRED where >75W in daylight zone. DIMMING per C405.2.3 item 1. C405.13 auto receptacle. Daylight + vacancy sensors for maximum savings.30–50 fc avg
Perim: 50 fc
ANSI/IES RP-3-20 §4
J3
Shop / Lab Classroom — K-12Vacancy Sensor Req'd · Timeclock Exempt50§2.1§2.3🔌§405.131.04C405.3
T.C405.3.2(2)
Shop/lab classroom: C405.2.1 item 1. C405.2.1.1 Exception 2 — shop classrooms and laboratory classrooms EXEMPT from manual-on requirement → auto-on ≤50% permitted. DIMMING per C405.2.3 item 1. C405.13 auto receptacle. C408.3.30–50 fc avg
ANSI/IES RP-3-20 §4
J4
Classroom · Full Integration — K-12Daylight + AV + Tunable White · C405.2.1§2.1§2.3§2.4📽🔌§405.130.72C405.3
T.C405.3.2(2)
Classroom — full integration: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4. DIMMING per C405.2.3 item 1. AV per C405.2.5 special application. Tunable white for learning. C405.13 auto receptacle. Full BMS. C408.3.30–50 fc avg
ANSI/IES RP-3-20 §4
J5
Natatorium / Indoor Pool — K-12Safety Exception · Full Auto-On§2.1§2.3§2.40.99C405.3
T.C405.3.2(2)
Natatorium K-12: C405.2.1 occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted (safety environment). DIMMING per C405.2.3. DAYLIGHT per C405.2.4 (skylights). Wireless for wet environment. C408.3.50 fc avg surface
IES RP-6-15 §6
J6
Gymnasium — K-12Occ Sensor · AV · Daylight50§2.1§2.3§2.4📽0.82C405.3
T.C405.3.2(2)
Gymnasium K-12: C405.2.1 occ sensor. Auto-on ≤50%. DIMMING per C405.2.3 item 4 — REQUIRED for gymnasiums. DAYLIGHT per C405.2.4 (skylights). AV for events/scoring. C405.2.8 demand-responsive. C408.3.30–50 fc practice
IES RP-6-15 §4
J7
Cafeteria / Dining Hall — K-12Occ Sensor REQUIRED — C405.2.1 Mandatory List50§2.1§2.3📽0.36C405.3
T.C405.3.2(2)
Cafeteria K-12: C405.2.1 item 6 — cafeteria requires occ sensor. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF. DIMMING per C405.2.3 item 3 (cafeteria dining). AV for events. C405.2.8 demand-responsive. C408.3.20–30 fc avg
IES HB 10th Ed.
J8
Cafetorium — K-12Cafetorium (Cafeteria + Auditorium) · Zone Controls · Dimming Required50§2.1§2.3📽0.82C405.3
T.C405.3.2(2)
Cafetorium (combined cafeteria/auditorium hybrid space). Compliance path: use higher LPD (gym playing area 0.82 W/SF (2025 NYCECC)) to cover all modes. C405.2.1 item 6 (cafeteria) — occ sensor required. C405.2.1.3 if ≥300 SF — zone controls ≤600 SF. C405.2.3 item 3 — dimming required (dining) and item 2 (auditorium use). AV integration for assembly use. C405.2.8 demand-responsive. C408.3.20–50 fc avg
ANSI/IES RP-3-20 + HB
J9
Gymnastorium — K-12Gymnastorium (Gymnasium + Auditorium) · Dimming Required · AV Integrated50§2.1§2.3§2.4📽0.82C405.3
T.C405.3.2(2)
Gymnastorium (combined gymnasium/auditorium). Use gymnasium playing area LPD 0.75 W/SF. C405.2.1 occ sensor. Auto-on ≤50%. C405.2.3 item 4 — dimming REQUIRED (gymnasium). C405.2.4 daylight responsive if skylights present. AV integration for assembly/event use. Scene control for gym vs. assembly modes. C405.2.8. C408.3.30–75 fc avg
Sport: 50–75 fc
IES RP-6-15 + HB
J10
Laboratory Classroom — K-12Vacancy Sensor REQUIRED · High-Task Illumination · C405.2.1 Item 1§2.1§2.3🔌§405.131.04C405.3
T.C405.3.2(2)
C405.2.1 item 1 — classrooms/training rooms require occ sensor. C405.2.1.1 Exception 2 — NOTE: laboratory classrooms are EXEMPT from the manual-on requirement; auto-on ≤50% permitted. C405.2.3 item 1 — dimming required. C405.13 item 1.5 — auto receptacle. Per Table C405.3.2(2): "Laboratory — in or as a classroom" = 1.04 W/SF. C408.3.50–75 fc avg
Bench: 75 fc
ANSI/IES RP-3-20 §4
J11
Art / Maker Space — K-12Vacancy Sensor REQUIRED · High CRI · Task + Ambient · C405.2.1 Item 1§2.1§2.31.04C405.3
T.C405.3.2(2)
C405.2.1 item 1 — classroom/training rooms. C405.2.1.1 Exception 2 — art rooms (non-shop/lab) require manual-on (vacancy). C405.2.3 item 1 — dimming required. Tunable white for color accuracy (CRI ≥90, 3500–5000K range). Use laboratory classroom LPD 1.04 W/SF as closest space type. C408.3.50 fc avg
Task: 75 fc
ANSI/IES RP-3-20 §4
K
UNIVERSITIES & HIGHER EDUCATION
Higher education classrooms and lecture halls require vacancy sensor per C405.2.1. Athletic pools: safety exception. Lecture halls: vacancy sensor + AV. Libraries: occ sensor + tunable white.
9 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
K1
Lecture Hall / AuditoriumVacancy Sensor · AV Integrated · Daylight§2.1§2.3§2.4📽0.72C405.3
T.C405.3.2(2)
Lecture hall: C405.2.1 item 1 — classrooms/lecture. C405.2.1.1 Exc 2: VACANCY required. DIMMING per C405.2.3 item 1 — REQUIRED. DAYLIGHT per C405.2.4. AV integration for presentations. C405.2.8. C408.3.30–50 fc avg
ANSI/IES RP-3-20 §5
K2
Library / Study CommonsOcc Sensor · Tunable White · Daylight50§2.1§2.3§2.40.86C405.3
T.C405.3.2(2)
Library/study commons: C405.2.1 occ sensor. DIMMING per C405.2.3 item 7 — REQUIRED for library reading rooms. DAYLIGHT per C405.2.4. Tunable white for reading. C405.2.8 demand-responsive. C408.3.30–50 fc avg
ANSI/IES RP-30-25 §5
K3
University Athletics / Gym / Rec CenterOcc Sensor · AV · Daylight50§2.1§2.3§2.4📽0.82C405.3
T.C405.3.2(2)
University gym/rec: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 — REQUIRED (gyms/fitness centers). DAYLIGHT per C405.2.4. AV for events. C405.2.8 demand-responsive. C408.3.30–50 fc avg
IES RP-6-15 §4
K4
Natatorium / Indoor Pool — UniversitySafety Exception · Full Auto-On§2.1§2.3§2.40.99C405.3
T.C405.3.2(2)
University natatorium: C405.2.1 occ sensor. C405.2.1.1 Exc 1 — full auto-on (safety). DIMMING per C405.2.3. DAYLIGHT per C405.2.4 (skylights). Wireless for wet environment. C408.3.50 fc avg surface
IES RP-6-15 §6
K5
Field House / ArenaOcc Sensor · AV · Daylight50§2.1§2.3§2.4📽0.82C405.3
T.C405.3.2(2)
Field house/arena: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 (large gym). DAYLIGHT per C405.2.4. AV for events. C405.2.8 demand-responsive. Zone control per luminaire group. C408.3.75–100 fc playing
IES RP-6-15 §3
K6
Cafeteria / Dining Hall — UniversityOcc Sensor REQUIRED · AV Integration50§2.1§2.3📽0.36C405.3
T.C405.3.2(2)
University cafeteria: C405.2.1 item 6. C405.2.1.3 zone controls ≥300 SF. DIMMING per C405.2.3 item 3 (cafeteria dining). AV. C405.2.8 demand-responsive. C408.3.20–30 fc avg
IES HB 10th Ed.
K7
University / Research LaboratoryVacancy Sensor · High Task Illumination · Lab LPD 1.21 W/SF§2.1§2.3§2.4🔌§405.131.21C405.3
T.C405.3.2(2)
C405.2.1 item 17 (≤300 SF) or item 1 (classroom/lab). C405.2.1.1 — vacancy sensor (manual-on). C405.2.3 — dimming required. C405.2.4 — daylight responsive where >75W sidelit. C405.13 auto receptacle (lab workstations = individual workstations per 1.7). Table C405.3.2(2): "Laboratory — otherwise" = 1.21 W/SF. C408.3.50–100 fc avg
Bench: 75–100 fc
ANSI/IES RP-3-20 §6
K8
Cafetorium — UniversityCafetorium · Zone Controls REQUIRED ≥300 SF · C405.2.1.350§2.1§2.3📽0.82C405.3
T.C405.3.2(2)
University cafetorium (cafeteria + auditorium). C405.2.1 item 6 — occ sensor required. C405.2.1.3 ≥300 SF zone controls. C405.2.3 items 2 + 3 — dimming required. AV for assembly. Use gymnasium playing area LPD 0.75 W/SF. C405.2.8 demand-responsive (Group E ≥10,000 SF). C408.3.20–50 fc avg
ANSI/IES RP-3-20 + HB
K9
Dormitory Living QuartersC405.2.10 Exception — Manual Controls Permissible · Dimming Required§2.30.46C405.3
T.C405.3.2(2)
Dormitory living quarters. C405.2.10 Exception — dwelling/sleeping units may use manual controls. C405.2.3 — dimming still required. Tunable white for circadian wellness (not code-mandated). C405.3.3: lamp efficacy requirements apply. Table C405.3.2(2): "Dormitory — living quarters" = 0.46 W/SF. C408.3.5–30 fc avg
IES HB 10th Ed.
L
PUBLIC & CIVIC SPACES
Courtrooms and secure government spaces may qualify for safety/security exception per C405.2.1.1 — consult DOB. Museums and performance venues require timeclock per C405.2.2 (no occ sensor in those spaces per design intent).
8 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
L1
Museum / GalleryManual Scene · Timeclock · Tunable White§2.2§2.30.31C405.3
T.C405.3.2(2)
Museum/gallery: NOT in C405.2.1 mandatory list → C405.2.2 TIME-SWITCH REQUIRED. DIMMING per C405.2.3 item 11 (spaces without C405.2.1.1). C405.2.5 Exception: display/accent/track lighting EXEMPT (special application). Tunable white for conservation. C408.3.5–30 fc exhibit
IES HB 10th Ed.
L2
Transit Hub / Transportation CenterFull Auto-On · Safety · Daylight§2.1§2.3§2.40.71C405.3
T.C405.3.2(2)
Transit hub: C405.2.1 occ sensor (public space). C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. 24-hr operation consideration. C405.2.8 demand-responsive. C408.3.10–20 fc avg
ANSI/IES RP-10-20 §4
L3
Performance Venue / AuditoriumManual Scene · Timeclock · AV · TW§2.2§2.3📽1.09C405.3
T.C405.3.2(2)
Performance venue: C405.2.2 TIME-SWITCH required (not in C405.2.1 list). DIMMING per C405.2.3 item 11. C405.2.5 Exception: theatrical/performance lighting with automated scene control EXEMPT from C405.2.3. AV integration. Tunable white. C408.3.10–20 fc seating
IES HB 10th Ed.
L4
Courthouse / Government OfficeOcc Sensor · Daylight · Security Exception50§2.1§2.3§2.41.06C405.3
T.C405.3.2(2)
Courthouse/gov office: C405.2.1 item 8 (offices). Auto-on ≤50%. DIMMING per C405.2.3 item 10 (offices). DAYLIGHT per C405.2.4. C405.2.8 demand-responsive (Group B). C408.3.50–75 fc avg
IES HB 10th Ed.
L5
CourtroomOcc Sensor · High-Task Illumination · Courtroom LPD 1.08 W/SF50§2.1§2.3📽1.08C405.3
T.C405.3.2(2)
C405.2.1 occ sensor (enclosed space). Auto-on ≤50%. C405.2.3 — dimming required. AV integration for video proceedings. C405.2.8 demand-responsive (Group B courthouse). Table C405.3.2(2): "Courtroom" = 1.08 W/SF (2025 NYCECC). C408.3.50–75 fc avg
Bench: 75 fc
IES HB 10th Ed.
L6
Religious Building — Worship / Choir / PulpitTime-Switch REQUIRED · Scene Control · Special Application Exception§2.2§2.3📽0.75C405.3
T.C405.3.2(2)
Religious worship space — not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required. C405.2.5 — theatrical/performance lighting for worship is special application (scene control exempt). AV. Tunable white for atmosphere. Table C405.3.2(2): religious — worship/pulpit/choir 0.75 W/SF. C408.3.30–50 fc avg
Choir: 50 fc
IES HB 10th Ed.
L7
Religious Building — Fellowship HallTime-Switch REQUIRED · Dimming Required · Multi-Purpose Use§2.2§2.30.50C405.3
T.C405.3.2(2)
Fellowship hall / multipurpose religious space. C405.2.2 time-switch required. C405.2.3 item 11 — dimming required. Table C405.3.2(2): religious buildings — fellowship hall 0.50 W/SF. C408.3.20–30 fc avg
IES HB 10th Ed.
L8
Convention Center — Exhibit SpaceTime-Switch REQUIRED · Dimming · C405.2.8 Demand-Responsive§2.2§2.30.50C405.3
T.C405.3.2(2)
Convention center exhibit hall. Not in C405.2.1 mandatory list → C405.2.2 time-switch REQUIRED. C405.2.3 item 11 — dimming required. C405.2.8 demand-responsive (Group B/M ≥10,000 SF). C405.2.5 display/accent lighting exempt. Table C405.3.2(2): convention center exhibit space 0.50 W/SF. C408.3.30–50 fc avg
Exhibit: 50 fc
IES HB 10th Ed.
M
PARKING
Interior parking: C405.2.4 special garage controls apply. Zones ≤3,600 SF reduce ≥30% within 15 min. Entrance/exit zones reduce ≥50% sunset to sunrise. Exterior: astronomical timeclock REQUIRED per C405.2.6. Dim to ≤50% — NOT full off (safety).
6 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
M1
Interior Parking Garage — StandardC405.2.4 Garage Controls · Safety · Full Auto-On§2.1§2.3§2.40.11C405.3
T.C405.3.2(2)
C405.2.9 — SPECIFIC PARKING CONTROLS: occ sensor + auto-reduce ≥30% in each zone (≤3,600 SF) within 15 min. C405.2.9 item 3: within 20 ft of wall openings — auto-reduce ≥50% in response to daylight. C405.2.9 item 2: eye adaptation at entries — reduce ≥50% sunset to sunrise. DIMMING per C405.2.3.5–10 fc avg
ANSI/IES RP-10-20 §4
M2
Interior Parking Garage — Vacancy PathManual-On · Safety Dim · C405.2.4§2.1§2.3§2.40.11C405.3
T.C405.3.2(2)
C405.2.9 parking controls. Vacancy sensor option per C405.2.1.1. Auto-reduce ≥30% per zone. DAYLIGHT per C405.2.4 at openings. DIMMING per C405.2.3. C408.3.5–10 fc avg
ANSI/IES RP-10-20 §4
M3
Parking Garage · Daylit Entry RampsDaylight at Ramps · C405.2.3 + C405.2.4§2.1§2.3§2.41.06C405.3
T.C405.3.2(2)
C405.2.9 item 2: entry ramp eye-adaptation lighting — SEPARATELY CONTROLLED, reduce ≥50% from sunset to sunrise. C405.2.9 item 3: within 20 ft of perimeter openings — daylight-responsive ≥50% reduction. C405.2.3 dimming. C408.3.10–20 fc transition
ANSI/IES RP-10-20 §4
M4
Parking Garage · Ingress/Egress ZoneDark Adaptation Zone · Safety · C405.2.4§2.1§2.3§2.41.06C405.3
T.C405.3.2(2)
Dark adaptation zone: C405.2.9 item 2 — REQUIRED separate control at vehicle entrances; reduce ≥50% from sunset to sunrise. C405.2.9 item 3 daylight at openings. DIMMING per C405.2.3. C408.3.10–20 fc transition
ANSI/IES RP-10-20 §4
M5
Open-Air / Surface Parking LotAstronomical Timeclock REQUIRED · C405.2.6§2.2§2.4N/AExterior
C405.2.7
Surface parking lot — exterior: C405.2.7.1 auto-off when daylight adequate. C405.2.7.3: luminaires >40W at ≤24 ft — reduce ≥50% when no activity for 15 min. Astronomical timeclock. Daylight sensor. C408.3.2–5 fc avg
ANSI/IES RP-8-25 §6
M6
Parking Garage · Stair / Elevator CoreFull Auto-On · Life Safety · C405.2.1.4§2.1§2.30.47C405.3
T.C405.3.2(2)
Garage stair/elevator core: C405.2.1 item 15 — stairways require occ sensor. C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3. C405.2 Exception 2: life safety paths within exit stairways exempt from auto-off. C408.3.5–10 fc avg
NFPA 101
N
WAREHOUSE & INDUSTRIAL
WAREHOUSE RULE — C405.2.1.2: Occ sensor auto-on to FULL power; reduce ≥50% when unoccupied. This is the EXCEPTION to the standard ≤50% auto-on rule. Full power auto-on required for warehouse/industrial only. NOT full off — forklift/pedestrian safety requires minimum illumination.
5 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
N1
Warehouse — General Storage (High-Bay)C405.2.1.2 Warehouse Rule · ≥50% Reduction50§2.1§2.3§2.41.24C405.3
T.C405.3.2(2)
C405.2.1 item 16: warehouse storage REQUIRES occ sensor. C405.2.1.2 SPECIFIC: each AISLEWAY controlled independently; auto-reduce to ≤30% (not full-off) within 15 min; backup time-switch for non-sensored areas; manual off provided. DAYLIGHT at skylights per C405.2.4. C405.2.8.20–30 fc avg
IES RP-7-22 §5
N2
Warehouse — Daylit High-BaySkylights · C405.2.1.2 + C405.2.350§2.1§2.3§2.41.24C405.3
T.C405.3.2(2)
C405.2.1.2 aisle-by-aisle controls. DAYLIGHT per C405.2.4 — REQUIRED at skylights. C402.5.2.2: skylight haze factor >90% for warehouse. Combined daylight + occ sensor. DIMMING per C405.2.3. C405.2.8. C408.3.20–30 fc avg
IES RP-7-22 §5
N3
Loading Dock / Receiving AreaC405.2.1.2 · Daylight at Dock Doors50§2.1§2.3§2.40.51C405.3
T.C405.3.2(2)
Loading dock: C405.2.1.2 warehouse controls apply. DAYLIGHT per C405.2.4 at dock doors. DIMMING per C405.2.3. Zone control per dock bay. C405.2.8 demand-responsive. C408.3.20–30 fc avg
IES RP-7-22 §7
N4
Warehouse Mezzanine Office / Break RoomVacancy Sensor · Commercial Office Rules Apply§2.1§2.3🔌§405.130.73C405.3
T.C405.3.2(2)
Mezzanine office/break room: C405.2.1 items 5 and 8 (breakroom + office). C405.2.1.1 Exc 2: vacancy. DIMMING per C405.2.3. C405.13 auto receptacle (office/break). C405.2.8. C408.3.30–50 fc avg
ANSI/IES RP-1-24 §4
N5
Cold Storage / Freezer WarehouseManual-On · Low-Temp Fixtures§2.1§2.30.35C405.3
T.C405.3.2(2)
Cold storage/freezer: C405.2.1 item 12 — storage rooms require occ sensor. Vacancy sensor (manual-on for cold entry). DIMMING per C405.2.3. Wired for cold-rated fixtures. Manual-on accommodates glove use in cold environment. C408.3.10–20 fc avg
IES RP-7-22 §5
O
DATA CENTERS
Server rooms EXEMPT from automatic controls per C405.2.2 Exception items 2 & 4 (safety/security/continuous operation). LPD applies to architectural lighting only — IT equipment loads excluded from LPD calculation.
3 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
O1
Data Center — Server / Computer RoomSafety + Continuous Operation Exception · C405.2.2§2.30.75C405.3
T.C405.3.2(2)
C405.2.1 item 2 — data centers require occ sensor. C405.2 Exception 1: 24/7 continuous operations — auto-shutoff would endanger systems → MANUAL controls permissible. DIMMING per C405.2.3. Wired control for precision lighting management. C408.3.20–30 fc avg
IES HB 10th Ed.
O2
Data Center — Network Operations CenterLow Auto-On · Occ Sensor · Screen Glare Control50§2.1§2.30.75C405.3
T.C405.3.2(2)
NOC/operations center: C405.2.1 item 2 — computer rooms require occ sensor. Auto-on ≤50%. DIMMING per C405.2.3. Wired + wireless. C405.2.8 demand-responsive. C408.3.30–50 fc avg
IES HB 10th Ed.
O3
Data Center — Electrical / MechanicalVacancy Sensor · NEC 700 Emergency Required§2.1§2.30.71C405.3
T.C405.3.2(2)
C405.2.1 item 17: enclosed ≤300 SF. Vacancy sensor. DIMMING per C405.2.3. C405.2.5: task lighting for electrical work may qualify for special application. C408.3.20 fc avg
IES HB 10th Ed.
P
SUPPORT & UTILITY
Janitor closets, restrooms, copy rooms, and break rooms are EXPLICITLY NAMED in C405.2.1.1 mandatory occ sensor list. Most commonly missed spaces during NYC DOB inspection. Electrical/mechanical rooms require NEC 110.26(D) maintenance override.
13 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
P1
Electrical Room / Switchgear / MCCVacancy Sensor · NEC 110.26(D) Override Required§2.1§2.30.71C405.3
T.C405.3.2(2)
C405.2.1 item 17: enclosed ≤300 SF — occ sensor. Vacancy (manual-on). DIMMING per C405.2.3. C405.2.5: task lighting exempt. NFPA 70E: manual control appropriate for arc flash safety. C408.3.20–30 fc avg
IES HB 10th Ed.
P2
Main Mechanical Room / HVAC PlantVacancy Sensor · Override Required · NEC 110.26(D)§2.1§2.30.71C405.3
T.C405.3.2(2)
C405.2.1 occ sensor. Vacancy sensor. DIMMING per C405.2.3. C405.2.5 task lighting for mechanical work exempt. C408.3.20–30 fc avg
IES HB 10th Ed.
P3
Generator Room / Emergency Power RoomEXEMPT — Manual Required · NFPA 37 · NFPA 1100.71C405.3
T.C405.3.2(2)
Generator room: C405.2 Exception 1 — AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT SAFETY — EXEMPT from occ sensor requirements. Manual controls only. No dimming required (safety-critical/emergency space). C408.3.10–20 fc avg
IES HB 10th Ed.
P4
Plumbing / Fire Sprinkler Valve RoomVacancy Sensor · NFPA 13§2.1§2.30.71C405.3
T.C405.3.2(2)
C405.2.1 item 17: enclosed ≤300 SF. Vacancy sensor. DIMMING per C405.2.3. NFPA 13 sprinkler access — manual-on appropriate. C408.3.20–30 fc avg
IES HB 10th Ed.
P5
Utility Service Corridor / Basement HallFull Auto-On · C405.2.1.4 Dim to ≤50%50§2.1§2.30.44C405.3
T.C405.3.2(2)
Utility corridor: C405.2.1 item 15 — corridors require occ sensor. C405.2.1.4: reduce to ≤50% within 15 min. DIMMING per C405.2.3 item 11. Wired zone control. C408.3.5–10 fc avg
ANSI/IES RP-28-25 §4
P6
Basement / Below-Grade StorageVacancy Sensor REQUIRED · C405.2.1.1§2.1§2.30.35C405.3
T.C405.3.2(2)
C405.2.1 item 12 — storage rooms require occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3.10–20 fc avg
IES HB 10th Ed.
P7
Janitor's Closet / Custodial RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1§2.1§2.30.35C405.3
T.C405.3.2(2)
C405.2.1 item 18 — SPECIFICALLY LISTED: janitorial closets require occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3.10 fc avg
IES HB 10th Ed.
P8
Telecom / IDF / MDF ClosetEXEMPT — Security + Continuous Operation · C405.2.2§2.30.71C405.3
T.C405.3.2(2)
Telecom/IDF/MDF: C405.2 Exception 1 — security systems require continuous lighting; auto-shutoff could endanger security operations — EXEMPT. Manual controls. DIMMING per C405.2.3. Wired for permanent installation. C408.3.10–20 fc avg
IES HB 10th Ed.
P9
Restroom / Toilet Room / Locker RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1§2.1§2.30.74C405.3
T.C405.3.2(2)
C405.2.1 item 11 — RESTROOMS specifically required. C405.2.1.1 Exception 1: full auto-on permitted for restrooms. DIMMING per C405.2.3. Wired multi-stall management. C408.3.20 fc avg
IES HB 10th Ed.
P10
Copy / Print / Mail RoomVacancy Sensor REQUIRED — Explicitly Named · C405.2.1.1§2.1§2.3🔌§405.130.50C405.3
T.C405.3.2(2)
C405.2.1 item 4 — COPY/PRINT ROOMS specifically listed. C405.2.1.1 Exc 2: vacancy required. DIMMING per C405.2.3. C405.13 item 1.3 — AUTO RECEPTACLE REQUIRED for rooms used primarily for copy/print. C405.2.8. C408.3.30 fc avg
IES HB 10th Ed.
P11
Laundry / Service RoomVacancy Sensor · Continuous Cycle Exception Possible§2.1§2.30.43C405.3
T.C405.3.2(2)
C405.2.1 item 9 — LAUNDRY/WASHING specifically listed. Vacancy sensor. DIMMING per C405.2.3. Wired for utility space. C408.3.20 fc avg
IES HB 10th Ed.
P12
Workshop / Fabrication ShopVacancy Sensor · High-Task · Workshop LPD 1.09 W/SF§2.1§2.31.09C405.3
T.C405.3.2(2)
C405.2.1 item 17 (≤300 SF enclosed) or occ sensor for larger. Vacancy sensor. C405.2.3 — dimming required. C405.2.5 — task lighting over equipment may qualify as special application. Table C405.3.2(2): "Workshop" = 1.09 W/SF. C408.3.50–75 fc avg
Bench: 75 fc
IES HB 10th Ed.
P13
Locker Room / Changing RoomFull Auto-On Permitted · C405.2.1.1 Exception 1 · Dimming Required§2.1§2.30.43C405.3
T.C405.3.2(2)
C405.2.1 item 14 — locker rooms REQUIRE occ sensor. C405.2.1.1 Exception 1 — full auto-on permitted for locker rooms (explicitly listed). C405.2.3 — dimming required. Table C405.3.2(2): "Locker room" = 0.43 W/SF. C408.3.20–30 fc avg
IES HB 10th Ed.
Q
COMMERCIAL HIGH-RISE OFFICE (>75 ft / 7+ Stories)
All 2025 NYCECC C405.2 controls apply. ADDITIONALLY: NYC Local Law 88 (LL88) — tenant submetering required for spaces >5,000 SF. NYC Local Law 97 (LL97) — carbon intensity reporting required, LPD compliance directly impacts carbon penalty calculations.
8 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
Q1
Class A Open Office FloorZone Controls C405.2.1.3 · LL88 Submetering · LL9750§2.1§2.3§2.4📽§2.1.3🔌§405.130.56C405.3
T.C405.3.2(2)
Class A open floor: C405.2.1.3 REQUIRED — zone controls ≤600 SF; auto-on ≤20% unoccupied zones; auto-off all zones ≤15 min. DAYLIGHT per C405.2.4. DIMMING per C405.2.3 item 10. AV. Partition sensors. Tunable white. C405.13 items 1.6–1.7. C405.2.8.25–40 fc avg
ANSI/IES RP-1-24 §4.2
Q2
Class A Private Office · PerimeterVacancy Sensor · Daylight · Shades · TW · LL97§2.1§2.3§2.4🔌§405.130.73C405.3
T.C405.3.2(2)
Class A private office: C405.2.1.1 Exc 2: vacancy. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 10. Tunable white. C405.13 item 1.1 auto receptacle. C405.2.8. C408.3.30–50 fc avg
ANSI/IES RP-1-24 §4.1
Q3
Class A Conference RoomVacancy Sensor · AV · Daylight · Shades · LL88§2.1§2.3§2.4📽🔌§405.130.88C405.3
T.C405.3.2(2)
Class A conference: C405.2.1.1 Exc 2: vacancy required. DAYLIGHT per C405.2.4 + automated shades. DIMMING per C405.2.3 item 2. AV. Tunable white. C405.13 item 1.2 auto receptacle. C405.2.8. C408.3.30–50 fc avg
ANSI/IES RP-1-24 §5
Q4
High-Rise Building LobbyFull Auto-On · Tunable White · LL88 Metered§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
High-rise lobby: C405.2.1.1 Exc 1 — full auto-on permitted. DIMMING per C405.2.3 item 8 — REQUIRED (lobbies). DAYLIGHT per C405.2.4. C405.2.8 demand-responsive. Tunable white for brand. C408.3.20–30 fc avg
ANSI/IES RP-1-24 §7
Q5
High-Rise Elevator Lobby / CoreFull Auto-On · Dim on Vacancy · C405.2.1.450§2.1§2.30.64C405.3
T.C405.3.2(2)
Elevator lobby/core: C405.2.1.4 — treated as corridor; reduce to ≤50% within 15 min; full shutoff NOT permitted. DIMMING per C405.2.3. Wired zone control per floor. C408.3.5–10 fc avg
ANSI/IES RP-28-25
Q6
High-Rise Base Building CorridorFull Auto-On · C405.2.1.4 Dim · LL9750§2.1§2.30.44C405.3
T.C405.3.2(2)
Base building corridor: C405.2.1.4 REQUIRED — reduce to ≤50% within 15 min; NOT full off. DIMMING per C405.2.3 item 11. Wired zone control per corridor segment. C408.3.5–10 fc avg
ANSI/IES RP-28-25
Q7
High-Rise Mechanical / Electrical FloorVacancy Sensor · NEC 110.26(D) · C405.2.1.1§2.1§2.30.71C405.3
T.C405.3.2(2)
C405.2.1 item 17: enclosed ≤300 SF — occ sensor. Vacancy sensor. DIMMING per C405.2.3. C408.3.20 fc avg
IES HB 10th Ed.
Q8
High-Rise Rooftop AmenityOcc Sensor Interior · Astro TC Exterior · LL9750§2.1§2.2§2.3§2.40.76C405.3
T.C405.3.2(2)
Rooftop amenity (interior+exterior): Interior zones: C405.2.1 occ sensor. Exterior zones: C405.2.7 timeclock + C405.2.7.3 setback. C405.2.2 time-switch for exterior. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. Tunable white. C408.3.10–30 fc avg
IES HB 10th Ed.
R
COMMERCIAL HIGH-RISE RESIDENTIAL (>75 ft)
Dwelling units EXEMPT from occ sensors and timeclocks per C405.2.1 and C405.2.2 residential exceptions. All common areas, corridors, amenities, and parking require full C405.2 compliance. NYC LL88 and LL97 apply to base building and common areas.
7 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
R1
High-Rise Dwelling UnitManual Only · Residential Exception · Tunable White§2.30.46C405.3
T.C405.3.2(2)
High-rise dwelling unit: C405.2.10 Exception — MANUAL controls permissible (no occ sensor). DIMMING per C405.2.3. Tunable white for circadian (not code-mandated). Wireless for tenant control. C408.3 for any automated systems.5–20 fc avg
IES HB 10th Ed.
R2
High-Rise Amenity LevelFull Integration · Occ Sensor · AV · LL88 · LL9750§2.1§2.3§2.4📽0.44C405.3
T.C405.3.2(2)
High-rise amenity level: C405.2.1 occ sensor. DIMMING per C405.2.3. DAYLIGHT per C405.2.4. AV + automated shades for event flex. Tunable white. C405.2.8. C408.3.15–30 fc avg
IES HB 10th Ed.
R3
High-Rise Residential CorridorFull Auto-On · C405.2.1.4 · LL9750§2.1§2.30.44C405.3
T.C405.3.2(2)
Residential corridor: C405.2.1.4 — REDUCE TO ≤50% within 15 min; full shutoff NOT permitted. DIMMING per C405.2.3. Wired zone control per floor. C408.3.5–10 fc avg
ANSI/IES RP-28-25
R4
High-Rise Residential LobbyFull Auto-On · Daylight · LL88 Metered§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
Residential lobby: C405.2.1.1 Exc 1 — full auto-on. DIMMING per C405.2.3 item 8 — REQUIRED (lobbies). DAYLIGHT per C405.2.4. Tunable white. C405.2.8. C408.3.20–30 fc avg
ANSI/IES RP-1-24 §7
R5
High-Rise Fitness Center / GymOcc Sensor · Tunable White · Daylight · LL9750§2.1§2.3§2.40.82C405.3
T.C405.3.2(2)
Residential fitness: C405.2.1 occ sensor. DIMMING per C405.2.3 item 4 — REQUIRED (gyms/fitness). DAYLIGHT per C405.2.4. Tunable white for workout/recovery. C405.2.8. C408.3.30–50 fc workout
IES RP-6-15 §5
R6
High-Rise Rooftop TerraceInterior Occ Sensor · Exterior Astro TC · LL9750§2.1§2.2§2.3§2.4N/AExterior
C405.2.7
Rooftop terrace (exterior): C405.2.7 exterior controls. C405.2.7.3: reduce ≥50% at midnight. C405.2.2 time-switch for scheduled events. Interior occ sensor for any enclosed zones. DAYLIGHT per C405.2.4. Tunable white. C408.3.2–10 fc avg
IES G-1
R7
High-Rise Residential ParkingC405.2.4 Garage Controls · Safety · LL88§2.1§2.3§2.40.11C405.3
T.C405.3.2(2)
C405.2.9 residential parking: auto-on + ≥30% reduction per zone ≤3,600 SF. DAYLIGHT per C405.2.9 item 3 at openings. DIMMING per C405.2.3. C408.3.5–10 fc avg
ANSI/IES RP-10-20 §4
S
INSTITUTIONAL & CORRECTIONAL
Correctional facilities, jails, detention centers, psychiatric wards, and secure institutional buildings. Emergency lighting and security lighting circuits are fully exempt from C405.2 controls (NEC 700/517). All general lighting must comply with C405.2.3 dimming. Corridor lighting dims to ≤50% per C405.2.1.4 — full shutoff prohibited in occupied security zones. Daylighting often restricted by security design requirements — C405.2.3 exemptions may apply where glazing is absent.
8 SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
OCC
SENSOR
TIME
CLOCK
MAN
DIM
MAN
OVRD
DAY
DIM
OCC
EXEMPT
DIM
CTRL
EMER
CIRC
ASTRO
TC
S1
Secure Corridor / Housing Unit CorridorCorrectional Facility · C405.2.1.4 Dim-Only · No Full Shutoff 50§2.1 §2.2 §2.3 📽 0.44C405.3
T.C405.3.2(2)
Secure corridor: C405.2.1.4 — reduce to ≤50%; NEVER full off (security). C405.2.2 time-switch backup. DIMMING per C405.2.3. Security/CCTV integration via wired control only. AV for intercom. C408.3. 5–10 fc avg
ANSI/IES RP-28-25
S2
Inmate Housing Cell / Detention Room<400 SF · C405.2.1 Occ Sensor · Vacancy Preferred §2.1 §2.2 §2.3 📽 0.52C405.3
T.C405.3.2(2)
Detention cell: C405.2.1 item 17 (≤300 SF enclosed). Vacancy sensor. C405.2.2 time-switch. DIMMING per C405.2.3. NOTE: C405.2 Exception 1 — security-critical cells may require manual controls. Security/AV integration. C408.3. 10–20 fc avg
IES HB 10th Ed.
S3
Correctional Program Room / Classroom500–3,000 SF · Occ Sensor · Auto-On ≤50% · Dimming Required 50§2.1 §2.2 §2.3 📽 0.74C405.3
T.C405.3.2(2)
Correctional classroom: C405.2.1 item 1. C405.2.1.1 Exc 2: vacancy required for classrooms. C405.2.2 time-switch. DIMMING per C405.2.3. Security AV integration. C408.3. 30–50 fc avg
ANSI/IES RP-3-20 §4
S4
Psychiatric Ward / Behavioral Health UnitC405.2.1 Occ Sensor · C405.2.1.1 Exception · Patient Safety Controls §2.1 §2.2 §2.3 📽 0.78C405.3
T.C405.3.2(2)
Psychiatric ward: C405.2.1 occ sensor. C405.2.1.1 Exc 1: full auto-on (patient safety). C405.2.2 time-switch. DIMMING per C405.2.3 item 5 (healthcare). Automated shades for behavioral therapy. Security AV. C408.3. 5–20 fc avg
ANSI/IES RP-29-25
S5
Correctional Cafeteria / Dining Hall500–5,000 SF · C405.2.1 Occ Sensor · Timeclock if No Sensor 50§2.1 §2.2 §2.3 📽 0.36C405.3
T.C405.3.2(2)
Correctional cafeteria: C405.2.1 item 6. C405.2.1.3 zone controls ≥300 SF. C405.2.2 time-switch. DIMMING per C405.2.3 item 3. Security AV. C408.3. 15–25 fc avg
IES HB 10th Ed.
S6
Institutional Office / Administrative SuitePrison Admin · 500–3,000 SF · Vacancy Sensor · Timeclock §2.1 §2.2 §2.3 📽 0.73C405.3
T.C405.3.2(2)
Institutional office: C405.2.1 item 8 (office). Vacancy. C405.2.2 time-switch. DIMMING per C405.2.3 item 10. Security AV/intercom. C408.3. 30–50 fc avg
ANSI/IES RP-1-24
S7
Exterior Perimeter / Yard Security LightingCorrectional Exterior · C405.2.6 Astro TC · ≥50% Setback Not Always Permitted §2.2 §2.4 §2.1.3 N/AExterior
C405.2.7
Exterior security perimeter: C405.2.7 exterior controls. C405.2.7.1 daylight auto-off. C405.2.7.3 setback. C405.2 Exception 1: security perimeter — full shutoff may be restricted. Manual override required. C405.2.2 time-switch. Wired security integration. Motion detection. C408.3. 1–5 fc avg
IES G-1
S8
Infirmary / Institutional Medical Room<500 SF · NEC 517 Healthcare Essential Electrical · Auto-On Full §2.1 §2.2 §2.3 📽 1.16C405.3
T.C405.3.2(2)
Institutional infirmary: C405.2.1 occ sensor. C405.2.1.1 Exc 1: full auto-on (clinical). C405.2.2 time-switch. DIMMING per C405.2.3 item 5 (healthcare exam). Automated shades. Security + medical integration. C408.3. 30–75 fc avg
IES HB §26 / RP-29
T
HOSPITALITY & HOTEL
Hotels, motels, and hospitality venues. Guestrooms: C405.2.10 sleeping unit exception — manual controls permissible. Lobbies: full auto-on + dimming required per C405.2.3. Corridors: reduce to ≤50% per C405.2.1.4. Banquet/event spaces: time-switch + scene control.
5 SPACE TYPES SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
T1
Hotel / Motel GuestroomC405.2.10 Exception · Manual Controls Permissible · Dimming Required§2.30.41C405.3
T.C405.3.2(2)
Hotel/motel guestroom. C405.2.10 Exception — sleeping units may use manual controls (no occ sensor required). C405.2.3 — dimming required. Tunable white for hospitality circadian (not code-mandated). C405.3.3 lamp efficacy requirements apply. Table C405.3.2(2): Guestroom = 0.41 W/SF. C408.3.5–30 fc avg
IES HB 10th Ed.
T2
Hotel Lobby / ReceptionFull Auto-On Permitted · Dimming REQUIRED · C405.2.3 Item 8§2.1§2.3§2.40.80C405.3
T.C405.3.2(2)
C405.2.1.1 Exception 1 — full auto-on permitted (lobbies). C405.2.3 item 8 — DIMMING REQUIRED for lobbies. C405.2.4 daylight responsive where >75W sidelit. C405.2.8 demand-responsive (Group R-1 ≥10,000 SF). Tunable white for brand identity. Table C405.3.2(2): Lobby otherwise = 0.80 W/SF. C408.3.20–50 fc avg
ANSI/IES RP-1-24 §7
T3
Hotel Corridor / Guest FloorOcc Sensor Dims to ≤50% — Full Shutoff NOT Permitted · C405.2.1.450§2.1§2.30.44C405.3
T.C405.3.2(2)
C405.2.1.4 SPECIFIC RULE — occ sensor SHALL reduce to ≤50% power within 15 min; FULL SHUTOFF NOT PERMITTED. C405.2.3 dimming required. Wired zone control per floor segment. Table C405.3.2(2): Corridor otherwise = 0.44 W/SF. C408.3.5–10 fc avg
ANSI/IES RP-28-25 §4
T4
Banquet / Ballroom / Event SpaceTime-Switch REQUIRED · Scene Control · C405.2.5 Special Application§2.2§2.3📽0.76C405.3
T.C405.3.2(2)
Ballroom/banquet/event space. Not in C405.2.1 mandatory list — C405.2.2 TIME-SWITCH REQUIRED. C405.2.3 item 3 — dimming required (dining). C405.2.5 — theatrical/scene control qualifies as special application. AV integration. Tunable white. Table C405.3.2(2): Dining — bar/lounge/leisure = 0.76 W/SF (2025 NYCECC). C408.3.15–30 fc avg
Event: 50 fc
IES HB 10th Ed.
T5
Hotel Fitness CenterOcc Sensor · Dimming REQUIRED · C405.2.3 Item 4 (Gymnasiums)50§2.1§2.30.82C405.3
T.C405.3.2(2)
C405.2.1 occ sensor. Auto-on ≤50%. C405.2.3 item 4 — DIMMING REQUIRED (gymnasiums/fitness centers). Tunable white for workout and recovery. C405.2.8 demand-responsive. Table C405.3.2(2): Gymnasium/fitness — exercise area = 0.82 W/SF (2025 NYCECC). C408.3.30–50 fc workout
IES RP-6-15 §5
V
AUTOMOTIVE & VEHICLE
Vehicular maintenance facilities, emergency vehicle garages, and commercial parking structures. Auto service bays require occ sensor + dimming per C405.2.3. Emergency vehicle garages: full auto-on permitted. Indoor parking: C405.2.9 specific parking controls.
3 SPACE TYPES SPACE TYPES
⬡ CODE SPACE / AREA TYPE OCCUPANCY CONTROLS MANUAL CONTROLS SPECIALTY CONTROLSPLUG LOAD
CONTROL
MAX LPD
W/SF
CONTROL NARRATIVE · 2025 NYCECC CITATION IES FC TARGET
AUTO-ON
FULL
AUTO-ON
≤50%
VAC
SNSR
TIME
CLK
MAN
ONLY
DIM WIRED
CTL
WRLS
CTL
DAYLT
C405.2.4
AV SHADES PART TUN
WHITE
PLUG
LOAD
C405.13
V1
Vehicular Maintenance / Auto Service BayOcc Sensor · Auto-On ≤50% · Vehicular Maintenance LPD 0.53 W/SF50§2.1§2.30.53C405.3
T.C405.3.2(2)
C405.2.1 occ sensor required. Auto-on ≤50%. C405.2.3 — dimming required. C405.2.8 demand-responsive (Group S ≥10,000 SF). C405.2.5 — task lighting over vehicles may qualify as special application. Table C405.3.2(2): Vehicular maintenance area = 0.53 W/SF. C408.3.30–50 fc avg
Pit/lift: 50 fc
IES HB 10th Ed.
V2
Emergency Vehicle Garage / Fire Station BayFull Auto-On Permitted · C405.2.1.1 Exception 1 · Safety Override§2.1§2.30.41C405.3
T.C405.3.2(2)
C405.2.1 occ sensor (large enclosed space). C405.2.1.1 Exception 1 — full auto-on permitted (safety environments). C405.2.3 dimming. C405.2 Exception 1 may apply for emergency dispatch bays where auto-shutoff would endanger safety. Table C405.3.2(2): Emergency vehicle garage = 0.41 W/SF. C408.3.20–30 fc avg
IES HB 10th Ed.
V3
Indoor Parking Garage — CommercialC405.2.9 SPECIFIC PARKING CONTROLS · Zone Reduction + Daylight at Openings§2.1§2.3§2.40.11C405.3
T.C405.3.2(2)
C405.2.9 SPECIFIC PARKING CONTROLS: occ sensor + auto-reduce ≥30% per zone ≤3,600 SF within 15 min. Item 2: vehicle entry eye-adaptation — reduce ≥50% sunset to sunrise. Item 3: within 20 ft of perimeter openings or skylights — auto-reduce ≥50% in response to daylight. C405.2.3 dimming. Table C405.3.2(2): Parking area interior = 0.11 W/SF. C408.3.5–10 fc avg
ANSI/IES RP-10-20 §4
General Notes — 2025 NYCECC
Provide control devices with required power pack, room controller, or other device as shown on plan per manufacturer specifications.
Zoning: provide per light type or as shown on plan; all zones shall have distinct control circuits per C405.2.1.3.
Control stations: coordinate configuration, number, height, and location with ADA requirements per ICC A117.1.
LPD: all spaces shall not exceed max LPD per 2025 NYCECC Table C405.3.2(1). LPD applies to all permanently installed lighting.
NYC LL88: Buildings >25,000 SF — tenant electrical submetering required for each tenant space >5,000 SF. Coordinate with LL88 requirements simultaneously with NYCECC compliance.
NYC LL97: Carbon intensity reporting required. Lighting LPD compliance directly impacts carbon penalty calculations. Class B office: 0.00846 tCO2e/SF by 2030.
⚡ REV 63 — C405.13 AUTO RECEPTACLE CONTROL: Effective with 2025 NYCECC enforcement (March 30, 2026), automatic plug load control is MANDATORY in all offices, conference rooms, and open work areas. At minimum, 50% of 125V, 15A & 20A receptacles in these spaces must be on controlled circuits that auto-de-energize with the occupancy sensor (15-min timeout). Controlled receptacles must be marked with △ per C405.13.1. Provide at least one always-on hot receptacle per workstation. Coordinate controlled receptacle switching with the lighting control panel or a dedicated plug load controller relay output. See note E and C405.13 code modal for full requirements.
Controls Notes — 2025 NYCECC Citations
A. DIMMING — C405.2.3 (2025 NYCECC): MANDATORY for general lighting in: classrooms/lecture halls/training rooms, conference/multipurpose/meeting rooms, dining areas (bar/lounge, leisure, family), gymnasiums/fitness centers, healthcare imaging rooms/exam rooms/nurseries/nurses' stations, laboratories, library reading rooms, lobbies, lounge/break rooms, offices (all), and spaces not provided with occupant sensor controls per C405.2.1.1. Control function (C405.2.3.1): Manual controls shall allow continuous dimming from full output to 10% of full power or lower, plus full off. Manual dimmer control required within each room. Exception: High-end trim controls exempt if calibration accessible only to authorized personnel and users cannot override above trim setpoint. Exception: Luminaires with special application controls per C405.2.5.
B. DAYLIGHT RESPONSIVE CONTROLS — C405.2.4 (2025 NYCECC): MANDATORY when installed general lighting wattage within a daylight zone exceeds the trigger threshold below. Applies to each zone independently — exceeding the threshold in one zone does not require controls in others.
Zone TypeWattage TriggerZone Depth (from glazing face)Glazing Qualification
Primary Sidelit>75 WLesser of: 1× window head height or 15 ftVert. glazing ≥24 SF, VT ≥0.20
Secondary Sidelit>150 WFrom primary zone edge to lesser of: 2× head height or 20 ftSame fenestration as primary
Toplit — Skylights>75 W0.7× ceiling height in all directions from skylight edgeSkylight area ≥24 SF per zone
Toplit — TDDs>75 W0.7× ceiling height from TDD edge≥0.1 SF aperture per device
Zone wattage count: Sum rated input wattage of all general lighting luminaires whose photometric center falls within the zone boundary. Task, decorative, and C405.2.5 special application fixtures are excluded. Luminaires straddling the boundary within 2 ft of the perimeter may be counted at 50%. Control function (C405.2.4.1): Continuous dimming from full output to ≤15% of full rated light output (not wattage) before shutoff. Complete shutoff capability required. Step dimming is not permitted. Independent zone control required: toplit zones separate from sidelit; primary separate from secondary; each cardinal façade orientation separately controlled. Calibration accessible only to authorized personnel. When occupant sensor reduces to unoccupied setpoint, daylight controls continue operating but may not increase power above unoccupied setpoint. Commissioning (C408.3.1.3): All daylight controls shall be calibrated and functionally tested by an approved agency prior to final inspection. Verification confirms field calibration, ≤15% dim floor, smooth continuous response, and zone independence. Exceptions: (EX 1) Healthcare spaces where patient care is directly provided — patient rooms, OR, ICU, exam/treatment, nurseries (corridors, lobbies, and offices NOT exempt). (EX 2) Sidelit zones on the ground floor above grade in Group A-2 and M occupancies (toplit zones on ground floor are NOT exempt). (EX 3) Enclosed offices <250 SF. Design guide: Primary zone depth = window head height (e.g., 9 ft head → 9 ft primary zone; 12 ft head → 12 ft primary, 12–20 ft secondary). Toplit zone radius = 0.7× ceiling height (e.g., 14 ft ceiling → 9.8 ft radius; 28 ft warehouse ceiling → 19.6 ft radius). Raise head heights and use high-VT glazing to maximize daylit area per zone and reduce the number of independently controlled zones.
C. AV INTEGRATION: Refer to AV integration note on drawings per C405.2.3. Coordinate scene presets with AV contractor. Scene presets must include ≤20% level for AV/presentation mode.
D. MOTORIZED SHADES: Provide fully integrated shade connection with lighting controls system. Coordinate shade position with daylight sensor per C405.2.4. Shade position shall be communicated to the daylight responsive control system so that the photosensor setpoint can be adjusted based on shade deployment state. When shades are fully closed, the daylight control system shall operate from a stored setpoint for overcast/no-daylight conditions. Coordinate shade schedule with WELL Building Standard v2 L04 (Daylight) where applicable.
E. AUTOMATIC RECEPTACLE CONTROL — C405.13 (2025 NYCECC): REV 63 — C405.13 MANDATORY. Automatic receptacle control is required for ≥50% of all 125V, 15A and 20A receptacles in the following space types: enclosed offices, conference rooms, copy/print rooms, breakrooms, classrooms, open plan office areas, and individual workstations (including modular partitions/workstation systems). Additionally, ≥25% of branch circuit feeders installed for modular furniture not shown on construction documents must be controlled.

Control method — one of the following (C405.13.1): (2.1) Timeclock — scheduled time-of-day control, programmable per day, zone ≤5,000 SF and ≤1 floor, 2-hour manual override permitted, override switch controls ≤5,000 SF; (2.2) Occupant sensor — turns off receptacles within 15 minutes of all occupants leaving; (2.3) Automated signal from another control/alarm system — off within 15 minutes of determining unoccupied.

Receptacle configuration (C405.13.1 item 1): Either provide split controlled receptacles with the top receptacle controlled, or provide a controlled receptacle within 12 inches of each uncontrolled receptacle.

Marking (C405.13.1 item 3): All controlled receptacles shall be permanently marked per the NYC Electrical Code and be uniformly distributed throughout the space. Plug-in devices do not comply (C405.13.1 item 4).

Exceptions: (1) Receptacles for continuous operation equipment (24/7/365); (2) Spaces where auto control would endanger safety/security; (3) Within a single modular workstation, uncontrolled receptacles may be >12 in. but ≤72 in. from controlled receptacles.
F. PARTITION SENSOR: Rooms act independently when partition in place; zones unify when partition removed. Each partition zone separately zoned per C405.2.1.3.
G. TUNABLE WHITE: Tunable white controls with circadian programming per IES TM-18. CCT range 2700K–6500K. Coordinate with WELL Building Standard v2 L07.
H. DEMAND RESPONSIVE LIGHTING CONTROLS — C405.2.8 (2025 NYCECC): MANDATORY for interior general lighting in Group B (Business), E (Educational), M (Mercantile), and S (Storage) occupancies — covering not less than 75% of interior floor area. Upon receipt of a utility/grid demand response (DR) signal: (1) Reduce lighting output to ≤80% of full power (or ≤80% of high-end trim setpoint if trim is set); (2) Dim gradually and continuously over not more than 15 minutes to achieve the DR setpoint; (3) Automatically restore to normal settings after the DR event ends. Exceptions (C405.2.8): Buildings <10,000 SF total Group B/E/M/S area; buildings where DR signal is not available from a controlling entity other than the owner; parking garages; ambulatory care facilities; outpatient clinics; physician or dental offices. Warehouse/storage areas exception: may switch off ≥25% of general lighting power rather than dimming. Coordination required with utility/grid aggregator for DR signal protocol (typically OpenADR 2.0 or BACnet). Commissioning per C408.3.1.6 required for buildings claiming C406.3.2 credits.
I. COMMISSIONING — C408.3 FUNCTIONAL TESTING (2025 NYCECC): MANDATORY per C405.1: Lighting controls shall be commissioned per C408.3 prior to passing final inspection. An approved agency shall provide evidence that all lighting and receptacle control systems have been tested to ensure control hardware and software are calibrated, adjusted, programmed, and in proper working condition. Testing protocols: Occupant sensors (C408.3.1.1): ≤7 sensors → test all; >7 → test ≥10% of each unique type/geometry; ≥30% fail → test all; verify auto-off timing, on-level, manual-on behavior, and no cross-zone false triggering. Time-switch controls (C408.3.1.2): Confirm programming (weekday/weekend/holiday), correct time/date, battery backup, and ≤2-hr override limit; simulate occupied and unoccupied conditions. Daylight controls (C408.3.1.3): Verify field calibration, setpoints, and response to available daylight. High-end trim (C408.3.1.4): Verify trim set, calibration secured, users cannot override above trim max. Documentation due within 90 days of CO (C408.3.2): Equipment location drawings, O&M manuals (setpoints, service contacts, maintenance schedules, recalibration schedule), and test results report with deficiency disposition.
2025 NYCECC Code Citations — Quick Reference
C405.2.1 OCCUPANT SENSOR CONTROLS: Required in 18 space types: (1) classrooms/lecture/training, (2) computer rooms/data centers, (3) conference/meeting/multipurpose, (4) copy/print rooms, (5) lounges/breakrooms, (6) cafeteria & fast food dining, (7) medical supply rooms (healthcare), (8) enclosed offices, (9) laundry/washing areas, (10) open plan offices, (11) restrooms, (12) storage rooms, (13) telemedicine rooms (healthcare), (14) locker rooms, (15) corridors/transition areas/stairways, (16) warehouse storage areas, (17) other spaces ≤300 SF enclosed by floor-to-ceiling partitions, (18) janitorial closets. Control function varies by space type — see C405.2.1.1 through C405.2.1.5. C405.2.1.1: Auto-on to ≤50% for standard spaces. Full 100% auto-on ONLY for: corridors, stairways, restrooms, primary entrances, lobbies, safety spaces.
C405.2.1.2: WAREHOUSE RULE — auto-on to FULL power; reduce ≥50% when unoccupied. NOT the standard ≤50% auto-on rule.
C405.2.1.3: Open office ≥300 SF — zones ≤600 SF. Occupied zone full. Adjacent vacant zones ≤20%. Full space ≤20% after all zones vacant.
C405.2.1.4: CORRIDOR DIM — reduce to ≤50%; FULL OFF NOT PERMITTED. Egress min. 1.0 fc at floor level must be maintained at all times.
C405.2.2 TIME-SWITCH CONTROLS: Required in areas NOT provided with occupant sensor controls per C405.2.1.1. Exceptions: (1) luminaires requiring specific application controls per C405.2.4; (2) spaces where patient care is directly provided. Function (C405.2.2.1): 7-day programmable clock; 7 day-types per week; automatic holiday shutoff (≥24 hr, then resumes normal); program backup ≥10 hr if power interrupted; manual override switch permits lighting on for ≤2 hr at a time, controlling area ≤5,000 SF; for unscheduled spaces — default programmed to turn off lights ≥12 hr/day. Mall/auditorium/sales/manufacturing/arena exception: override may exceed 2 hr (captive key) and area may exceed 5,000 SF (but <20,000 SF).
C405.2.3 DIMMING: Continuous dimming REQUIRED for general lighting in classrooms, conference rooms, dining, gymnasiums, healthcare, laboratories, libraries, lobbies, lounge/breakrooms, and all offices. Manual dimmer shall allow continuous dim from full output to ≤10% power plus full off. Step dimming is not permitted. One manual dimmer control per room or zone.
C405.2.4 DAYLIGHT CONTROLS: Wattage thresholds: Primary sidelit zone >75W trigger; Secondary sidelit >150W; Toplit (skylights/TDDs) >75W. Zone geometry: primary = 1× head height or 15 ft (lesser); secondary = 1–2× head height or 15–20 ft; toplit = 0.7× ceiling height radius. Qualifications: fenestration ≥24 SF, VT ≥0.20 (sidelit); skylight ≥24 SF (toplit). Control: continuous dim to ≤15% before shutoff; toplit, primary, secondary, and each cardinal orientation independently controlled. Commissioning: C408.3.1.3 required. See modal and Note B for full requirements.
C405.2.6: Exterior — astronomical timeclock REQUIRED. Daylig
Home Daylight Requirements
☀ Daylight Responsive Controls — C405.2.4
2025 NYCECC (2024 IECC base) · Enforcement March 30, 2026 · Table C405.3.2(2) · Section C405.2.4 & C405.2.4.1
41
Spaces Requiring Daylight Controls
3
Zone Types (Primary / Secondary / Toplit)
15%
Max Dim Floor Before Shutoff
3
Exceptions (Healthcare / A-2 & M / <250 SF Office)
Wattage Trigger Thresholds C405.2.4
Primary Sidelit
>75W
Depth: 1× head height or 15 ft (lesser)
Glazing: ≥24 SF, VT ≥0.20
Secondary Sidelit
>150W
Depth: 1–2× head height (15–20 ft cap)
Same fenestration as primary
Toplit — Skylights
>75W
Radius: 0.7× ceiling height from skylight edge
Aperture: ≥24 SF per zone
Toplit — TDDs
>75W
Radius: 0.7× ceiling height from TDD edge
Aperture: ≥0.1 SF per device
Wattage count: Sum rated input watts of all general lighting luminaires whose photometric center falls within the zone perimeter. Task, decorative, and C405.2.5 special application fixtures are excluded. Luminaires within 2 ft of the zone boundary may be counted at 50%.
Zone Depth Calculator Interactive
Window Head Height ft
Ceiling Height (toplit) ft
ZoneDepth / RadiusTriggerNotes
Depths are measured horizontally from the glazing face. Toplit radius measured from each skylight or TDD edge in all directions. All values are per 2025 NYCECC C405.2.4.
Wattage Threshold Checker Interactive
1. Select zone type
2. Enter fixture wattage in the zone
Number of fixtures fixtures
Watts per fixture W each
Enter fixtures above to check threshold.
Exception Eligibility Checker C405.2.4 EX 1–3
1. Is this a healthcare facility where patient care is directly provided?
Patient rooms, ICU, OR, exam/treatment, nurseries, emergency care
2. Is this a first-floor sidelit zone in a Group A-2 or M occupancy?
Restaurants, bars, nightclubs (A-2) or retail/mercantile (M) — ground floor only
3. Is this an enclosed office space with floor area <250 SF?
Applies per individual enclosed room — not to open plan areas
Spaces Requiring Daylight Controls 41 Spaces · C405.2.4 Click any row to jump to that space in the compliance table
Code Space Name Category LPD W/SF Zone Type / Notes Exception?
Control Function Requirements C405.2.4.1
RequirementCode Value
Minimum dim level before shutoff≤15% of full rated output
Dimming typeContinuous only — step dimming NOT permitted
Toplit vs. sidelit controlIndependent — separate zone controllers required
Primary vs. secondary sidelitIndependent — separately controlled
Different cardinal orientationsIndependent — N/S/E/W facades separate
Shutoff capabilityComplete shutoff required
Calibration accessAuthorized personnel only — no user override
Interaction with occ sensorDaylight may continue; cannot raise above unoccupied setpoint
Interaction with high-end trim15% floor = % of full rated output (not trim-adjusted)
Sensor type (preferred)Closed-loop photosensor (measures space illuminance)
Sensors per zoneOne per controlled daylight zone minimum
Commissioning requiredYes — C408.3.1.3 by approved agency before final insp.
Commissioning Checklist C408.3.1.3
Completed: 0 / 0
Pre-Commissioning Verification
Functional Testing (C408.3.1.3)
Documentation (C408.3.2 — Due within 90 days of CO)
Home What Changed
⚡ What Changed — 2016 → 2020 → 2025 → 2028
NYC Energy Code evolution across four cycles · This document reflects the 2025 NYCECC (Local Law 47 of 2026 · 2024 IECC base · ASHRAE 90.1-2022) · Enforcement: March 30, 2026
Enterprise Lighting Sales · Controls Department
Lighting Controls Evolution
2016 → 2020 → 2025 → 2028
Wall dimmers are dead. Every change that affects your next NYC submittal — in one place. The code is not going to start asking less of you.
Old: 2020 NYCECC · 2018 IECC Now: 2025 NYCECC · 2024 IECC + ASHRAE 90.1-2022 Enforcement: March 30, 2026
~10%
commercial site energy savings vs prior code
∞→600
open office zone limit SF — from none to 600
3
brand-new mandatory requirements in 2025
4→7
C405.2 sub-sections across code cycles
01 — The Legal Cascade: Why NYC Is Always Harder §28-1001.3.1
🌐
IECC (Federal)
ICC model code · Updated every 3 years · 2024 IECC current
🗽
NYSECCC (State)
Adopts IECC + NY amendments · Must exceed federal · 2025 ECCCNYS in effect Dec 2025
🏙️
NYCECC (NYC)
Adopts State + additional stringency · Legally must exceed State · NYC DOB enforced
📌 NYC Admin Code §28-1001.3.1: DOB must update the code every 3 years. Not optional. Baked into law. There is no off ramp.
02 — LPD Progression: Watts/SF by Space Type C405.3 · Table C405.3.2(2)
Lighting Power Density — 4 Code Cycles 2016 → 2025 → ~2028
Space Type
IES FC Min
2016 LPD
2020 LPD
2025 LPD ✦
~2028 Est.
Private Office
30–50 fc
0.92
0.87
0.82
~0.75
Open Office
30–50 fc
1.10
1.05
0.98
~0.88
Conference Room
30–50 fc
1.30
1.23
1.11
~1.00
Retail Sales
30–100 fc
1.60
1.56
1.44
~1.30
Classroom
30–50 fc
1.35
1.26
1.11
~1.00
Corridor
5–10 fc
0.50
0.50
0.41
~0.37
OR Suite
150+ fc
2.50
2.48
2.26
~2.05
Parking Garage
5 fc
0.19
0.19
0.15
~0.13
2016 LPD
2020 LPD
2025 LPD (this document)
~2028 Estimate
✦ Bars scaled to max 2.50 W/SF · IES FC per ANSI/IES RP-1-24, RP-29-25, RP-3-20
03 — Zone Sizes: The Ceiling Keeps Shrinking C405.2.1.3
Open Office Zone Count — 10,000 SF Floor Plate Example Zones Required
2016 NYCECC
1 zone
1 zone
2020 NYCECC
≤600 SF
≥11 zones
2025 NYCECC ✦
≤600 SF · strict grid · 17+ zones on a 10K SF floor
17+ zones
~2028 Est.
addressable / fixture-level likely
Fixture-lvl
🧮 A 10,000 SF open floor in 2025 requires 17+ independent zones. Installing 17 relay panels and wall dimmers is neither practical nor career-enhancing. Fixture-integrated addressable controls are the only scalable path.
2016 NYCECC
"It's Fine."
Open OfficeNO limit — one zone per floor
CorridorsOn/Off — full shutoff OK
ExteriorPhotocell only
DimmingOptional
2020 NYCECC
"Starting to Sweat."
Open Office>300 SF → ≤600 SF zones
Corridors≤50% dim — full off banned
ExteriorAstro timeclock required
DimmingREQUIRED general circuits
2025 NYCECC ✦
"No, Really. ALL of Them."
≤300 SF1 zone, no split required
301–600 SF1 zone ≤600 SF
601–1,200 SFMin. 2 zones ≤600 SF ea.
>2,400 SFFull grid — every zone ≤600 SF
04 — 2025's Three Game-Changers NEW IN 2025
≤50% Auto-On
C405.2.1.1 — NEW
  • Standard spaces: sensors trigger at ≤50% max
  • 100% OK only: lobbies, corridors, restrooms, stairways, healthcare, NEC 517
  • Warehouses: 100% auto-on — opposite rule (C405.2.1.2)
  • Requires driver-level precision — wall switches don't know %
🎚️
Dimming Everywhere
C405.2.2.2 — Expanded
  • Every general circuit: continuous dimming only
  • 0-10V: floor at 10% · DALI-2: floor at 1%
  • Step-switching = NON-COMPLIANT. Full stop.
  • NEC 700 / NEC 517 emergency circuits only exemption
🌙
Exterior Curfew
C405.2.6.2 — NEW
  • Astro timeclock: auto sunrise/sunset, no manual override
  • Midnight–6 AM: all exterior dims to ≤50%
  • Motion sensor restores 100% temporarily, then returns
  • Security perimeters: AHJ approval required for exemption
05 — C405.2 Full Compliance Matrix All 13 Sub-Sections
Every Requirement — Enforcement March 30, 2026 No asterisks · No grandfathering
Section Requirement Key Rule vs 2020
C405.2.1Occ/vacancy sensor spaces13 space types required↑ +2 types
C405.2.1.1Auto-on level — standard spaces≤50% of full power🆕 NEW
C405.2.1.1XAuto-on exceptions100% permitted — listed safety spacesClarified
C405.2.1.2Warehouse auto-on100% FULL power — inverse rule🆕 NEW
C405.2.1.3Open office zone size≤600 SF per zoneSame
C405.2.1.4Corridor unoccupied setback≤50% · full shutoff prohibited↑ Tighter
C405.2.2Timeclock (non-sensor spaces)2-hr max override · 7-day programmableClarified
C405.2.2.2Dimming — all general lightingContinuous dimming requiredReaffirmed
C405.2.3Daylight controls threshold>75W primary/toplit · >150W secondary↑ Lower trigger
C405.2.4Parking garage controls≤3,600 SF zones · 30% min setback↑ Tighter
C405.2.6Exterior astro timeclockAuto sunset/sunrise · no overrideSame
C405.2.6.2Exterior nighttime setback≤50% midnight–6 AM🆕 NEW
C405.13Automatic receptacle control≥50% of 125V outlets · offices / classrooms / conf rooms🆕 NEW
06 — The LL97 Multiplier: Double Jeopardy NYC LOCAL LAW 97
$268
per metric ton CO₂ penalty — from 2024
~35%
of LL97 exposure traceable to lighting
LL88
Lighting must be sub-metered separately in buildings >25K SF
2030
Penalty rates step UP again — Class B: 0.00846 tCO₂e/SF
▸ Every watt over LPD limit = CO₂ overage = LL97 fine. It's literally arithmetic.
▸ No compliant controls = DOB violations AND LL97 carbon penalties. Two bills. One bad spec.
▸ Smart, dimmable, sub-metered controls are now a financial instrument — not a compliance checkbox.
07 — ~2028 Outlook: What's Coming Next ASHRAE 90.1-2022 · ICC 2027 · LL32
HIGH CONFIDENCE
LPD Reduction 8–12%
ASHRAE 90.1-2022 drives it. Private office toward 0.78 W/SF. No space type escapes.
HIGH CONFIDENCE
Demand Response Mandatory
C405.6 from optional to required. Expect OpenADR 2.0 or auto-dim on utility signal.
MED CONFIDENCE
Wireless / Addressable Systems
600 SF zone limits only achievable with wirelessly-commissioning addressable fixtures.
MED CONFIDENCE
Performance-Based Path (LL32)
Local Law 32 mandates a performance compliance path by 2028 — measured vs. predicted energy.
LOW CONFIDENCE
Fixture-Integrated Sensors Required
Possible rule: sensors must be part of the luminaire assembly in spaces >1,000 SF.
LOW CONFIDENCE
LL97 + NYCECC Formally Linked
Exceeding LPD may directly trigger LL97 carbon fine exposure — penalty frameworks merge.
Filing date governs which code applies. Complete applications filed on or before March 29, 2026 comply with 2020 NYCECC. Applications filed on or after March 30, 2026 are subject to the 2025 NYCECC. Use the 2025 NYCECC version of COMcheck for all new filings. Source: NYC DOB · Local Law 47 of 2026.
Source: ELS Lighting Controls Evolution Briefing · Brian L. Fitzsimmons, Director of Lighting Controls · Enterprise Lighting Sales · enterels.com · 212-343-9300
Cooper Lighting Solutions — Brand Portfolio
Enterprise Lighting Sales  ·  REV 116 BF  ·  cooperlighting.com  ·  cooperlighting.ai
🏢 Interior Lighting Commercial · Office · Healthcare · Education · Industrial · Retail · Sports
HALO
Industry's broadest recessed portfolio — airtight, IC-rated, and fire-rated housings for new construction, retrofit, remodel, and healthcare across every trim style.
Metalux
Commercial LED troffers, strips, wraparound, and high-bay fixtures engineered for offices, schools, retail, healthcare, and industrial environments.
Corelite
Architectural healthcare luminaires — patient room, corridor, and exam/treatment fixtures with CRI ≥90 and tunable white for clinical environments.
NeoRay
Architectural direct/indirect pendants, linear coves, and recessed linear systems for open-plan offices, conference rooms, and lobbies.
Ametrix
High-output linear LED fixtures and performance troffers for demanding commercial, education, and healthcare interior applications.
iO Lighting
Integrated luminaire-level intelligent lighting fixtures with built-in BACnet/DALI sensors for open-plan office and commercial spaces.
Shaper
Modular architectural lighting systems — configurable shapes, angles, and connections for creative interior ceiling designs and retail environments.
Nemalux
Industrial-grade LED high-bay, low-bay, and harsh-environment fixtures for manufacturing, warehousing, and food-processing facilities.
InVue
Retail display and accent lighting — adjustable track, recessed MR16, and case lighting optimized for merchandise presentation and retail environments.
Ephesus
High-performance LED sports lighting — arenas, stadiums, and multipurpose facilities with broadcast-quality illumination and precision beam control.
Fail-Safe
Healthcare-grade luminaires — patient room, exam, and procedure lighting fixtures engineered for clinical environments and infection-control requirements.
Decorative Lighting Hospitality · Residential · Retail · Architectural
Portfolio
Decorative residential and hospitality luminaires — pendants, chandeliers, sconces, and ceiling fixtures in curated finish and style collections.
Lumark AP
Architectural post-top and area decorative luminaires with LED efficiency and traditional styling for urban streetscapes and campus pathways.
Lumiere
Premium decorative architectural lighting — feature pendants, wall sconces, and linear systems for hospitality, high-end retail, and corporate lobbies.
🌙 Exterior Lighting Roadway · Parking · Area · Site · Façade
McGraw-Edison
Commercial and industrial area luminaires — parking lots, roadways, building perimeters, and site lighting with high-lumen LED efficiency.
Lumark
Rugged exterior LED area lights and wall packs for parking structures, commercial properties, and industrial site perimeter lighting.
RSA Lighting
High-performance roadway, area, and sports exterior luminaires with advanced optics and controls integration for municipal and commercial applications.
🏛️ Commercial Lighting Controls NYCECC C405.2 Compliant · BACnet · DALI-2 · Wireless · AI-Enabled
WaveLinx NLC
Networked lighting control platform with BACnet/IP integration, luminaire-level sensing, scene control, scheduling, and daylight harvesting for C405.2 compliance.
WaveLinx DALI
DALI-2 addressable control platform providing individual fixture-level dimming, grouping, scene control, and diagnostic feedback over a two-wire digital bus.
Greengate
Commercial-grade occupancy and vacancy sensors, dimmers, and wall controls for code-compliant lighting control in offices, classrooms, and conference rooms.
ILC
Intelligent Lighting Controls — centralized digital lighting management with relay panels, dimming modules, and graphical software for large commercial buildings.
Hey Coop! A.I.
AI-powered predictive lighting automation platform using occupancy learning, energy analytics, and demand-response integration for smart building optimization.
MWS Modular Wiring
Pre-wired modular wiring systems accelerating installation of lighting and controls in open-plan offices, reducing labor and commissioning time.
🚨 Emergency Life Safety NEC Article 700 · Exempt from Energy Code Controls
AtLite
Emergency egress luminaires and exit signs — self-contained battery-backed fixtures for life-safety egress illumination per NEC Article 700.
Sure-Lites
Complete emergency and exit lighting line — LED exit signs, emergency combo units, bug-eye fixtures, and remote heads for commercial egress compliance.
⚠ Emergency Life Safety circuits are governed by NEC Article 700 and are fully exempt from 2025 NYCECC energy control requirements (C405.2 Exception 3). Do not apply occupancy sensors or energy controls to emergency circuits.
BubblyNet
Bluetooth Mesh wireless lighting control platform providing commissioning, scheduling, dimming, and occupancy control without physical wiring infrastructure.
Cristal Controls
Advanced lighting control solutions including DALI drivers, scene controllers, and smart dimming interfaces for architectural and commercial applications.
Enterprise Lighting Sales  ·  212-343-9300  ·  20 West 36th Street, 3rd Floor, NYC 10018   |   BubblyNet  ·  bubblynet.com   |   Cristal Controls  ·  cristalcontrols.com
⚠ Important Disclaimers & Limitations
This document is for reference and education only. Always verify with the Authority Having Jurisdiction.
For Reference and Education Only
This document is prepared for educational and reference purposes only. It does not constitute legal, engineering, or code compliance advice. Always consult the full 2025 NYCECC text and your project's Authority Having Jurisdiction (AHJ).
Always Verify with the AHJ
Code interpretations vary by jurisdiction, project type, and occupancy. The NYC Department of Buildings and the project AHJ have final authority on all code compliance determinations.
A Licensed Engineer Must Review All Designs
Lighting and controls designs must be reviewed and stamped by a licensed Professional Engineer (PE) or Registered Architect (RA) before submission to the NYC Department of Buildings.
Emergency Lighting Is Exempt from Energy Controls
Emergency lighting circuits governed by NEC Article 700 are fully exempt from 2025 NYCECC energy control requirements per C405.2 Exception 3. Never apply occupancy sensors or dimmers to emergency circuits.
LPD Values Are Maximum Limits — Not Design Targets
Maximum Lighting Power Density (LPD) values are code-mandated upper limits. Good lighting design should target significantly lower installed power while meeting IES illuminance recommendations.
2025 NYCECC Enforcement Date: March 30, 2026
The 2025 NYCECC is mandatory for all permit applications filed on or after March 30, 2026. Projects permitted before this date may use prior code. Verify permit date with the NYC DOB.
IES Footcandle Targets Are Recommendations
IES illuminance targets shown are from IES RP-1 and related standards and are design recommendations, not code requirements. Final illuminance levels must suit the specific tasks, occupants, and conditions of each space.
No Liability — Proprietary & Confidential
This document is proprietary to Enterprise Lighting Sales. Enterprise Lighting Sales assumes no liability for errors, omissions, or the application of information contained herein. Distribution without written consent is prohibited.