⚑ Key Sections Interior LPD — Space-by-Space Table 9.6.1 Building Area Method Table 9.5.1 Mandatory Controls 9.4.1 Automatic Shutoff 9.4.1.1 Daylight Controls 9.4.1.3 Exterior Lighting 9.4.3
ANSI/ASHRAE/IES Standard 90.1 · Section 9

ASHRAE 90.1
Lighting Reference

The national model energy standard referenced by the IECC and adopted in 40+ states. Section 9 governs interior and exterior lighting power density limits, mandatory controls, and compliance paths for commercial buildings.

StandardASHRAE 90.1-2022
Full TitleANSI/ASHRAE/IES Std 90.1
Lighting SectionSection 9
Adopted By40+ States · IECC Reference
AuthorityLocal AHJ
NYC Basis2025 NYCECC references 90.1
2
Compliance Paths
100+
Space Types in Table 9.6.1
40+
States Adopted
📋 Standard Overview
Note: ASHRAE 90.1 is adopted state-by-state and may be locally amended. Always confirm the adopted edition and any amendments with the Authority Having Jurisdiction (AHJ). NYC adopts ASHRAE 90.1 by reference through the 2025 NYCECC.
9.1 Scope

Applies to commercial buildings and high-rise residential buildings. Excludes single-family residences, multifamily buildings of three stories or less, and buildings using less than 3.4 BTU/h·ft² of fossil fuel energy.

9.2 Compliance

All mandatory provisions must be met. Then choose between the Building Area Method or Space-by-Space Method for demonstrating LPD compliance. Both paths require all mandatory controls.

9.7 Documentation

Compliance documentation must identify the compliance method used, list all spaces and their LPDs, confirm all mandatory controls are installed, and be made available to the AHJ upon request.

🔀 Compliance Paths — Section 9.5 & 9.6

ASHRAE 90.1 provides two methods for demonstrating interior lighting power compliance. Both require all mandatory provisions in Section 9.4.

Space-by-Space Method Section 9.6

Each space type is assigned its own LPD limit from Table 9.6.1. The installed power for each space must not exceed the limit for that space type. More granular — preferred for mixed-use or complex buildings.

  • More accurate for mixed occupancies
  • Uses Table 9.6.1 — 100+ space types
  • Allows higher LPD in demanding spaces
  • Required baseline for LEED/energy modeling
Building Area Method Section 9.5

A single LPD limit applies to the entire building based on its primary occupancy type from Table 9.5.1. Simpler to document but less flexible — the whole building must comply as one budget.

  • Simpler documentation
  • Uses Table 9.5.1 — ~25 building types
  • Good for single-occupancy buildings
  • Not suitable for mixed occupancies
🏗️ Building Area Method — Table 9.5.1 LPD Limits

Maximum Lighting Power Density (W/ft²) by building type. Total installed power for the building must not exceed: LPD × Gross Floor Area.

Important: The Building Area Method is only appropriate when a single occupancy type represents the entire building. For multi-tenant or mixed-use buildings, use the Space-by-Space Method (Section 9.6).
Building Type LPD — 90.1-2022 (W/ft²) LPD — 90.1-2019 (W/ft²) Change Notes
Automotive Facility0.750.82Service bays, showrooms, offices
Convention Center0.820.87Exhibit halls, meeting rooms
Courthouse0.890.93Courtrooms, offices, lobby
Dining — Bar/Lounge/Leisure0.991.07Ambient + decorative allowance
Dining — Cafeteria/Fast Food0.800.90
Dining — Family0.890.89
Dormitory0.610.61Residential spaces + common areas
Exercise Center0.720.72
Fire Station0.670.71
Gymnasium0.941.00Court + support spaces
Health Care Clinic0.870.87Outpatient only; hospital = higher
Hospital1.051.05Includes all clinical + support areas
Hotel/Motel0.750.82Guest rooms + common areas
Library0.830.83
Manufacturing Facility0.821.11↓↓Significant reduction in 2022
Motion Picture Theater0.760.76
Multi-family0.510.51High-rise residential (4+ stories)
Museum0.961.02Exhibit + support areas
Office0.640.79↓↓Significant reduction in 2022
Parking Garage0.150.18Interior parking structure
Penitentiary0.780.81
Performing Arts Theater1.191.39Stage lighting excluded per 9.1.4
Police/Fire Station0.870.87
Post Office0.710.74
Religious Building0.720.72Sanctuary + support areas
Retail0.841.05↓↓General retail; see Table 9.6.1 for accent
School/University0.720.87↓↓Classrooms, admin, common areas
Sports Arena0.910.91Practice facility only; competition = higher
Town Hall0.720.72
Transportation0.700.70Airports, train stations, bus terminals
Warehouse0.450.58Storage + distribution
Workshop1.051.05
Source: ANSI/ASHRAE/IES Standard 90.1-2022, Table 9.5.1. Values in W/ft² of gross lighted floor area. Verify current adopted edition and local amendments with the AHJ.
📐 Space-by-Space Method — Table 9.6.1 (Selected Spaces)

LPD limits by individual space type. Only selected high-use commercial space types are shown. Refer to the full ASHRAE 90.1-2022 standard for the complete table.

Space Type Building Category LPD — 2022 (W/ft²) LPD — 2019 (W/ft²) Controls Required
Office — Enclosed (≤250 ft²)Office0.720.98Occ sensor + daylight if applicable
Office — Enclosed (>250 ft²)Office0.720.98Occ sensor + daylight if applicable
Office — Open PlanOffice0.550.61Occ sensor required
Conference / Meeting RoomOffice0.900.97Occ sensor + dimming
Corridor / TransitionCommon0.410.41Occ sensor — reduce to 20% when vacant
Lobby — Office/GeneralCommon0.710.84Daylight zone controls if applicable
Lobby — HotelHotel0.951.06Dimming required
StairwayCommon0.490.49Occ sensor — reduce to 20%
RestroomCommon0.630.63Occ sensor required
Storage / Warehouse — Medium BayIndustrial0.580.58Occ sensor required
Storage / Warehouse — Fine MaterialIndustrial0.690.69Occ sensor required
Classroom / Lecture / TrainingEducation0.720.81Occ sensor + daylight controls
Gym — Exercise AreaExercise0.720.72Occ sensor required
Lounge / BreakroomOffice0.590.59Occ sensor required
Electrical / Mechanical RoomCommon0.420.42Occ sensor required
Kitchen — CommercialFood Service1.001.21Occ sensor or auto-shutoff
Dining — Family / CasualFood Service0.650.65Dimming + occ sensor
Retail — Sales Area (General)Retail0.841.10Daylight + occ as applicable
Retail — Accent (Addl. Allowance)Retail+0.40+0.40Additional allowance for display lighting
Patient RoomHealthcare0.620.62Occ sensor; night mode required
Exam / Treatment RoomHealthcare1.151.66Occ sensor; task + ambient separation
Parking — InteriorParking0.150.19Occ sensor — reduce to 30% when vacant
Partial table only. The full ASHRAE 90.1-2022 Table 9.6.1 contains 100+ space types. Consult the standard directly for spaces not listed here. Values in W/ft² of task area or room floor area as defined in the standard.
🎛️ Mandatory Controls — Section 9.4

These controls are required in ALL compliance paths. They are not optional and cannot be traded off against LPD credits.

9.4.1.1 Automatic Shutoff

Lighting in all spaces ≤5,000 ft² must have automatic shutoff via occupancy sensor or scheduled time clock. Time clock must have 7-day, holiday, and manual override.

  • Spaces ≤5,000 ft²: occupancy sensor
  • Larger spaces: time clock or occ sensor
  • Stairwells: occ sensor — reduce to 20% or off
  • Corridors: occ sensor — reduce to 20% or off
9.4.1.2 Space Control

Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting. Switch or dimmer must be readily accessible.

  • Independent control per enclosed space
  • Readily accessible to occupants
  • Multi-scene control allowed
  • Exception: spaces with automatic full shutoff
9.4.1.3 Daylight Zone Controls

Lighting in daylight zones must be independently controllable from non-daylit zones. Sidelit zones >120 ft² and toplit zones require photosensor-based dimming or stepped switching.

  • Primary sidelit zone: 1× window head height
  • Secondary sidelit zone: 2× window head height
  • Skylight zone: 0.7× ceiling height from skylight
  • Continuous dimming preferred over stepped switching
9.4.1.4 Occupancy Sensing

Required in: enclosed offices ≤250 ft², conference rooms, copy/print rooms, break rooms, restrooms, storage rooms, janitorial closets, and other spaces as required in Table 9.6.1.

  • Auto-off within 30 minutes of vacancy
  • Manual-on preferred (not auto-on)
  • Partial-off (dimming to 20%) acceptable in corridors
  • Dual-tech sensors preferred for large spaces
9.4.1.5 Exterior Controls

All exterior lighting must be controlled by a combination of a photosensor and time switch, or an astronomical time switch. Motion sensors may provide partial-off control.

  • Photosensor: off during daylight hours
  • Time switch: shutoff or reduction after curfew
  • Curfew reduction: 30% reduction after 11pm or business close
  • Exception: 24-hour facilities with documented need
9.4.2 Additional Interior Controls

Display and accent lighting must be controllable independently from general lighting. Hotel guest room controls must include a master shutoff at the room entry that turns off all fixed luminaires.

  • Display/accent: separate switching circuit
  • Hotel guest rooms: master entry shutoff
  • Decorative lighting: ≤1W/ft² additional allowance
  • Task lighting: must be separately switchable
🌙 Exterior Lighting — Section 9.4.3 & Table 9.4.3

Maximum exterior lighting power for site and building envelope. Values are in addition to any separately permitted parking structure lighting.

Exterior Application Lighting Zone Maximum Power Unit
Parking Areas & DrivesLZ20.10W/ft² paved area
Parking Areas & DrivesLZ30.13W/ft² paved area
Building FacadesLZ20.10W/ft² façade area
Building FacadesLZ3/LZ40.15W/ft² façade area
Walkways (narrow, <10 ft)LZ20.70W/linear ft
Walkways (wide, ≥10 ft)LZ20.14W/ft² walkway area
Plaza AreasLZ20.13W/ft² plaza area
Main Entry (per door)LZ220W per door
Other Doors / EntriesLZ210W per door
Sales CanopyAll0.60W/ft² canopy area
Drive-Through WindowAll400W per lane
Outdoor DiningLZ20.65W/ft² dining area
Vehicle Service Area (outdoor)All0.25W/ft² service area
Lighting Zones: LZ1 = Rural; LZ2 = Suburban/low commercial; LZ3 = Urban/high commercial; LZ4 = Urban core / entertainment. Determine the zone applicable to your project from the local jurisdiction or ASHRAE 90.1 Appendix B. Most NYC commercial projects fall in LZ3 or LZ4.
🏙️ Relationship to 2025 NYCECC
Where They Align
  • Both require occupancy sensors in enclosed spaces
  • Both require daylight zone dimming controls
  • Both share the same basic LPD framework
  • NYCECC Section C405 closely tracks ASHRAE 90.1 Section 9
  • Commissioning required by both (ASHRAE 90.1 Section 10)
Where NYC Is Stricter
  • NYC occ sensor auto-off: 15 minutes (ASHRAE = 30 min)
  • NYC plug load control: ≥50% of 125V, 20A receptacles
  • NYC demand response: required for Groups B/E/M/S ≥75%
  • NYC has additional amendments beyond base ASHRAE
  • NYC commissioning: required before final DOB inspection
For NYC projects: Always use the 2025 NYCECC reference as the controlling document. ASHRAE 90.1 is the national baseline; NYC amendments layer additional requirements on top. When in conflict, the more stringent requirement governs.
⚠️ Key Exemptions — Section 9.1.4
Emergency Egress Lighting

Emergency lighting required by life-safety codes (NEC Article 700) is exempt from Section 9 LPD and control requirements. Never apply occupancy sensors or dimmers to emergency circuits.

Stage / Theater / Studio

Lighting for theatrical, performance, and broadcast studio applications is exempt from LPD limits. Production lighting systems are excluded from the building's LPD budget calculation.

Specialized Process Lighting

Lighting required for industrial or manufacturing processes, medical procedures, or research that cannot be reduced without affecting the process is exempt from the standard.

Display / Case Lighting

Lighting inside display cases with transparent fronts is exempt from LPD limits. Lighting for art objects on loan from a museum or gallery is also exempt.

Lighting <100W per Space

Spaces where the total installed lighting power is less than 100W are exempt from LPD requirements but must still comply with all mandatory control provisions.

Exterior — Signage

Externally illuminated signs and internally illuminated signs are exempt from exterior LPD limits but must be controlled to turn off or reduce ≥30% after business hours per Section 9.4.3.